| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) PLEASE CLARIFY IF ANY ELECTRICAL WORK (CONDUITS, |
| | EQUIPMENT) IS BEING DONE WITHIN THE SCOPE OF THIS |
| | PERMIT AND IF YES PLEASE PROVIDE DETAILS/SPECS. FBC 107 |
| | |
| | -- ELECTRICAL DRAWINGS SUBMITTED ARE FOR THE ENTIRE |
| | CONSTRUCTION. PLEASE PROVIDE NOTES OR NARRATIVE |
| | INDICATING WHAT WILL BE COVERED UNDER THE FOUNDATION |
| | PERMIT. |
| | -- SUBELECTRICAL PERMIT REQUIRED TO COVER ANY |
| | ELECTRICAL RELATED WORK UNDER THE FOUNDATION PERMIT. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |