2021-01-15 17:50:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLETS IN BATHROOM CAN NOT SHARE OUTLETS IN LIVING
 AREA.
  
 210.11(C)(3) BATHROOM BRANCH CIRCUITS. IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 120-VOLT, 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY THE
 BATHROOM(S) RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL
 HAVE NO OTHER OITLET.
  
 2) PANELS SCHEDULE HAS DIFFERENT LOCATIONS FOR OUTLETS.
  