| 2021-01-06 14:55:03 | REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A GAS |
| | PERMIT FOR THE HEATER OUTSIDE. THIS IS UP TO THE |
| | HOMEOWNER TO MAKE AN APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. TANK TYPE WATER HEATERS ARE NOT MADE FOR OUTDOOR USE |
| | PER THE MANUFACTURERS SPECIFICATION UNLESS IN AN |
| | APPROVED STRUCTURE SUPPORTED BY THE MANUFACTURER. |
| | PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE UNIT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 4. PLEASE SUBMIT A GAS RISER ISOMETRIC DRAWING PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL GAS. |
| | |
| | 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1, |
| | G2413.4.2. |
| | |
| | 6. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 7. IS THIS THE ONLY GAS APPLIANCE AND THE TOTAL BTU |
| | LOAD ON THE SYSTEM? REFER TO THE 2017 FBC RES. SEC. |
| | G2413. |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2017 FBC RES. SEC. G2413.2. |
| | |
| | 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING |
| | ELEMENTS OF THE GAS VENT(S) PER THE 2017 FBC RES. SECS. |
| | G2426 THRU G2429.1. |
| | |
| | 10. THE GAS HEATER SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 11. SUBMIT A COPY OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE PLAN LISTING |
| | THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD |
| | USED IN THIS SYSTEM'S DESIGN PER THE 2017 FBC FG. 402.3 |
| | OR 2017 FBC RES. SEC. G2413.3. |
| | |
| | 12. PLEASE SHOW THE DISTANCE FROM THE TWO PSI REGULATOR |
| | TO THE APPLIANCE. COMPLY WITH 2017 FBC FG RES. TABLE |
| | G2413.4 (12) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | 13. GAS APPLIANCES (WATER HEATER) SHALL NOT BE |
| | PROHIBITED UNLESS IT COMPLIES WITH PER THE 2017 FBC |
| | RES. SEC. G2406.2. |
| | |
| | 14. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| | ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.1 GENERAL. |
| | |
| | 15. HOW IS THIS GAS VENTED AND IT IT NEAR A WINDOW, |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |