| Plan Review Notes For Permit 20121405 |
| Permit Number |
20121405 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-01-21 12:58:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET FP 1 - THERE IS AN INDICATION WITHIN A CLOUDED | | | REVISION SYMBOL OF 1" X 1/2' BUSHINGS INSTALLED ON 1 | | | INCH OUTLETS ON LEVELS 9-18. | | | | | | THERE IS ALSO A NOTE ON FLOOR PLAN SHEETS 9-18 STATEING | | | THE SAME. | | | | | | HOWEVER, THERE ARE NO INDICATION ON ANY FLOOR LAYOUT | | | SHEETS, 9-18, OF THE EXACT LOCATIONS OF THESE BUSHINGS | | | NOR IS THERE A SYMBOL THAT REPRESENTS THE PROPOSED | | | BUSHINGS. | | | | | | PLEASE REVIEW AND PROVIDE GREATER DETAILS AS TO THE | | | PROPOSED SPECIFIC LOCATIONS OF THESE BUSHINGS, AS WELL | | | AS, A REPRESENTABLE BUSHING SYMBOL. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|