| 2021-01-15 11:19:15 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20121402 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | GUEST COTTAGE |
| | 1) PLEASE SHOW THE CONDENSATE DRAIN MEETS FBC RES |
| | M1411.3.1 FOR AUXILIARY AND SECONDARY DRAIN SYSTEMS. |
| | |
| | 2) PLEASE SHOW THE CONDENSATE DISPOSAL ON SHEET M201. |
| | FBC RES M1411.3 |
| | |
| | 3) SHEET M101 FCU-1 INDICATES SUPPLY AIR CFM IS 635, |
| | SHEET M201 INDICATES 790 CFM FOR FCU-1 IN THE GUEST |
| | COTTAGE. PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | 4) SHEET M101 INDICATES FCU-1 IS A 1.5 TON UNIT, SHEET |
| | M201 INDICATES FCU-1 IS A 2 TON SYSTEM WITH 800 CFM |
| | SUPPLY AIR. PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | 5) SHEET M101 INDICATES CU-1 IS A 1.5 TON UNIT, SHEET |
| | M201 INDICATES THAT CU-1 IS A 2 TON UNIT. PLEASE BE |
| | CONSISTENT. FBC 107.2.1 |
| | |
| | MAIN HOUSE |
| | 1) PLEASE PROVIDE THE SPECIFICATIONS FOR THE RANGE. FBC |
| | 107.2.1 |
| | |
| | 2) PLEASE SHOW HOW THE FLEX DUCT IN THE GARAGE WILL |
| | MEET FBC RES M302.5.2 |
| | |
| | 3) PLEASE PROVIDE SPECIFICATIONS FOR THE BBQ GRILL. FBC |
| | 107.2.1 |
| | |
| | 4) PLEASE PROVIDE SPECIFICATIONS FOR THE BBQ HOOD. FBC |
| | 107.2.1 |
| | |
| | 5) SHEET M101 INDICATES THE SUPPLY AIR OF AHU-1-01 IS |
| | 2000 CFM, SHEET M201 COUNTING THE CFM?S OF EACH SUPPLY |
| | REGISTER FOR AHU-1-01 THE TOTAL SUPPLY IS 2086 CFM?S |
| | PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | 6) SHEET M101 INDICATES THE SUPPLY AIR FOR AHU-1-02 IS |
| | 800 CFM, SHEET M201 COUNTING THE CFM?S OF EACH SUPPLY |
| | REGISTER FOR AHU-1-02 THE TOTAL SUPPLY IS 888 CFM?S |
| | PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |