| Plan Review Notes For Permit 20121386 |
| Permit Number |
20121386 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-06 08:03:14 | 01/06/20 2ND GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON SHEET P-1, BOTH BATHROOMS ARE ON THE MAIN TRUNK | | | LINE, AND THEY NEED TO BE BRANCHED OFF FROM THE TRUNK | | | LINE AND VENTED AS A WET VENT SYSTEM. THIS WILL HAVE | | | THE WASHING MACHINE ON THE TRUNK LINE AFTER THE LAST | | | BATHROOM GROUP PER THE 2017 FBC SEC. R P3108.1 | | | HORIZONTAL WET VENT PERMITTED. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|