| 2021-01-28 16:54:22 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) BACK AND FRONT OF UNIT. GFI/WP OUTDOOR RECEPTACLES |
| | REQUIRED. NEC 210.8(A)(3) |
| | 2) LAUNDRY AREA: GFI RECEPTACLE REQUIRED. NEC |
| | 210.8(A)(10) |
| | 3) PANEL SCHEDULES A AND B: PLEASE PROVIDE AVAILABLE |
| | SHORT CIRCUIT CURRENT AT MAIN DISCONNECT AND SPECIFY |
| | AIC RATINGS FOR 250 AMPS DISCONNECT AND BOTH PANELS. |
| | 4) PLEASE SPECIFY IF PANELS HAVE MCB OR IF THEY MLO. |
| | FBC 107 |
| | 5) PLEASE SHOW AND IDENTIFY AND SHOW LOCATION OF |
| | DISCONNECTING MEANS FOR BOTH PANELS. PLEASE SPECIFY IF |
| | DISCONNECTS HAVE OCP AND IF YES SPECIFY BREAKER SIZES. |
| | FBC 107 |
| | 6) RISER DIAGRAM: PLEASE SPECIFY HOW FEEDER TO PANELS A |
| | AND B ARE PROTECTED. PANEL A FEEDER DOES NOT COMPLY |
| | WITH TAP RULES. IT ALSO SEEMS THAT DISTANCE FROM |
| | DISCONNECT TO PANEL B IS TOO LONG TO COMPLY WITH TAP |
| | RULES. SEE NOTES 4 AND 5 AS THESE ITEMS ARE RELATED. |
| | 7) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE WILL |
| | SUFFICE) |
| | 8) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE |
| | E4002.14 (A NOTE WILL SUFFICE) |
| | 9) NOTE 9 SPECIFIES A MINIMUM OF 50%. IT SHOULD BE 75%. |
| | SEE NOTE: PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT |
| | OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| | SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT |
| | OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |