| Plan Review Notes For Permit 20121374 |
| Permit Number |
20121374 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-04 09:54:44 | FIRE REVIEW COMMENTS: | | | | | | (1) CLARIFY THE GATE ENTRY (DRIVE THRU) SECURITY. THE | | | ENTRY MAY REQUIRE AN ACCESS BOX PER THE REQUIREMENTS OF | | | NFPA 1, FIRE CODE, 18.2.2 | | | | | | (2) WITH THE FENCE INSTALLATION, THE DISTANCE OF THE | | | FIRE HYDRANT TO THE FIRE DEPARTMENT CONNECTION NEEDS | | | CLARIFICATION TO DETERMINE IF ACCESS COMPLIES WITH THE | | | REQUIREMENTS OF NFPA 1, FIRE CODE, 18.5.3 | | | | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|