| 2023-05-09 06:09:12 | 1ST REVIEW FMC |
| | PERMIT: 20121361 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE APPLICATION DOES NOT MENTION ANY MECHANICAL WORK IN |
| | THIS BUILDING. THERE IS NO SCOPE OF WORK FOR THE |
| | MECHANICAL SYSTEMS. THERE IS NO INDICATION AS TO THE |
| | OCCUPANCY OF THIS BUILDING ON ANY DRAWINGS. SHEET M2.1 |
| | IS SHOWING A NEW RTU-9 BUT DOES NOT GIVE AN OCCUPANCY |
| | IN THE OUTDOOR AIR CALCULATIONS. IF THIS IS TO BE A |
| | SHELL BUILDING THAT WILL HAVE A CHANGE OF USE AND A |
| | COMPLETE MECHANICAL DESIGN AT THAT TIME PROVIDE A SCOPE |
| | OF WORK AND AN APPLICATION FOR WHAT IS BEING COMPLETED |
| | UNDER THIS PERMIT. FBC 107.3.5 |
| | |
| | 1) SHEET A-4 INDICATES THIS BUILDING TO BE AN I-2 |
| | OCCUPANCY. THE COMPLETE MECHANICAL DESIGN FOR THIS I-2 |
| | SHALL MEET THE REQUIREMENTS OF ASHRAE 170. FMC 407.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |