Plan Review Notes
Plan Review Notes For Permit 20121352
Permit Number 20121352
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-07 06:16:281) SHT. A1.4 - A MINIMUM OF ONE EXAM ROOM SINK SHALL
 COMPLY WITH THE FBC-ACCESS. SECS.212.1, 606.1.
 2) SHT. A1.1 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR
 SPACES AND THE TURNING DIAMETER IN THE ACCESSIBLE
 TOILET ROOMS. COMPLY WITH FBC-ACCESS. SECS.305.3,
 304.3.1.
 3) SHT. A1.3 - RESTROOM ELEVATIONS - SHOW THE HEIGHT OF
 THE PAPER DISPENSER OUTLET FROM THE FINISHED FLOOR. THE
 MAXIMUM HEIGHT OF THE OUTLET DISPENSER SHALL COMPLY
 WITH FBC-ACCESS. SECS.308.2 OR 308..3.
 4) SEPARATE FACILITIES ARE REQUIRED FOR MALES AND
 FEMALES PER FBC-PLUMBING SEC.403.2. ONE TOILET ROOM
 SHALL BE IDENTIIED FOR MALES AND ONE SHALL BE
 IDENTIFIED FOR FEMALES ON THE FLOOR PLAN.
 5) THE HUB DRAIN FOR THE WATER HEATER SHALL BE EQUIPPED
 WITH A TRAP PRIMER. FBC-PLUMBING SEC.1002..4.1.
 6) THE ICE MAKER/WATER DISPENSING LINE FO THE
 REFRIGERATOR SHALL BE EQUIPPED WITH A DUAL CHECK VALE
 BACKFLOW PREVENTER CCOMPLYING WITH ASSE 10224 PER
 FBC-PLUMBING SEC.608.3.
 7) AN AIR ARRESTOR SHALL BE INSTALLED ON THE WATER LINE
 FOR THE REFRIGERATOOR PER FBC-PLUMBING SEC.604.9.
 8) TEMPERED WATER IS REQUIRED ON THE LAVATORIES IN THE
 TOILET ROOMS PER FBC-PLUMBBING SEC.416.5. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED WATER-
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070
 OR CSA B125.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  