| 2021-01-07 06:16:28 | 1) SHT. A1.4 - A MINIMUM OF ONE EXAM ROOM SINK SHALL |
| | COMPLY WITH THE FBC-ACCESS. SECS.212.1, 606.1. |
| | 2) SHT. A1.1 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR |
| | SPACES AND THE TURNING DIAMETER IN THE ACCESSIBLE |
| | TOILET ROOMS. COMPLY WITH FBC-ACCESS. SECS.305.3, |
| | 304.3.1. |
| | 3) SHT. A1.3 - RESTROOM ELEVATIONS - SHOW THE HEIGHT OF |
| | THE PAPER DISPENSER OUTLET FROM THE FINISHED FLOOR. THE |
| | MAXIMUM HEIGHT OF THE OUTLET DISPENSER SHALL COMPLY |
| | WITH FBC-ACCESS. SECS.308.2 OR 308..3. |
| | 4) SEPARATE FACILITIES ARE REQUIRED FOR MALES AND |
| | FEMALES PER FBC-PLUMBING SEC.403.2. ONE TOILET ROOM |
| | SHALL BE IDENTIIED FOR MALES AND ONE SHALL BE |
| | IDENTIFIED FOR FEMALES ON THE FLOOR PLAN. |
| | 5) THE HUB DRAIN FOR THE WATER HEATER SHALL BE EQUIPPED |
| | WITH A TRAP PRIMER. FBC-PLUMBING SEC.1002..4.1. |
| | 6) THE ICE MAKER/WATER DISPENSING LINE FO THE |
| | REFRIGERATOR SHALL BE EQUIPPED WITH A DUAL CHECK VALE |
| | BACKFLOW PREVENTER CCOMPLYING WITH ASSE 10224 PER |
| | FBC-PLUMBING SEC.608.3. |
| | 7) AN AIR ARRESTOR SHALL BE INSTALLED ON THE WATER LINE |
| | FOR THE REFRIGERATOOR PER FBC-PLUMBING SEC.604.9. |
| | 8) TEMPERED WATER IS REQUIRED ON THE LAVATORIES IN THE |
| | TOILET ROOMS PER FBC-PLUMBBING SEC.416.5. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED WATER- |
| | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| | OR CSA B125.3. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |