| 2021-01-13 07:44:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | EXAM ROOMS ARE THEY TREATING PATIENTS IN THESE ROOMS, | | | WITH PROCEDURES, IF SO WIRING TO BE DONE IN ACCORDANCE | | | WITH 517.13 | | | | | | 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL | | | EQUIPMENT IN PATIENT CARE AREAS WIRING IN P ATIENT CARE | | | AREAS SHALL COMPLY WITH 517.13(A) AND (B). (A) WIRING | | | METHODS. ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS | | | SHALL BE PROVIDED WITH AN EFFE CTIVE GROUND-FAULT | | | CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM, | | | OR A CABLE HAVING A METALLIC ARMOR OR SHEATH ASSEMBLY. | | | THE METAL RACEWAY SYSTEM, OR METALLIC CABLE ARMOR, OR | | | SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT | | | GROUNDING CONDUCTOR IN ACCORDANCE WITH 250.118. | | | |
|