Plan Review Notes
Plan Review Notes For Permit 20121352
Permit Number 20121352
Review Stop E
Sequence Number 1
Notes
Date Text
2021-01-13 07:44:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 EXAM ROOMS ARE THEY TREATING PATIENTS IN THESE ROOMS,
 WITH PROCEDURES, IF SO WIRING TO BE DONE IN ACCORDANCE
 WITH 517.13
  
 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL
 EQUIPMENT IN PATIENT CARE AREAS WIRING IN P ATIENT CARE
 AREAS SHALL COMPLY WITH 517.13(A) AND (B). (A) WIRING
 METHODS. ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS
 SHALL BE PROVIDED WITH AN EFFE CTIVE GROUND-FAULT
 CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM,
 OR A CABLE HAVING A METALLIC ARMOR OR SHEATH ASSEMBLY.
 THE METAL RACEWAY SYSTEM, OR METALLIC CABLE ARMOR, OR
 SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT
 GROUNDING CONDUCTOR IN ACCORDANCE WITH 250.118.
  