| 2021-03-05 13:22:19 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20121350 |
| | 3/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAP LETTERS. THE REQUESTED COMMENT RESPONSE NARRATIVE |
| | WAS NOT PROVIDED. |
| | |
| | 1) FAILED. P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL |
| | TO SEAL THE ANNULAR SPACE AROUND THE NEW SINK DRAIN |
| | PIPING PENETRATIONS- SECTION 315.1 FBC P AND SECTION |
| | 714.4.1.2 FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN |
| | PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN |
| | ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED |
| | FLOOR TENDONS- SECTION 107.2.1 WPB. FIRESTOPPING NOT |
| | PROVIDED. |
| | |
| | 2) FAILED. SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN |
| | ONE, OF EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN |
| | COMPLIANCE WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE |
| | FOLLOWING DETAILS PER THE FBC ACC. REVISED SHEET A1.03 |
| | DOES NOT INDICATE CLEAR FLOOR SPACES FOR THE NEW |
| | ACCESSIBLE SINKS IN THE BREAKROOM AND OFFICE. |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | NEW SINKS- SECTIONS 212.3 AND 606. |
| | B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2, |
| | 305, & 306. |
| | C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE |
| | THE FINISH FLOORS- 606.3. |
| | |
| | 3) FAILED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE |
| | THAT INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING |
| | NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE |
| | SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH |
| | NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR |
| | WHAT THE REST OF THE SINKS IN THE ROOMS ARE TO BE USED |
| | FOR BECAUSE THEY ARE LISTED AS "BY OWNER". PLEASE |
| | CLARIFY THE USE OF THE SINKS AND NOTE THAT DEFERRED |
| | SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS MUST BE |
| | REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN |
| | CHARGE- SECTION 107.3.4.1 WPB. THREE NEW SINKS ARE |
| | BEING INSTALLED WHICH SHALL BE ACCESSIBLE. PLEASE |
| | PROVIDE THE REQUESTED SINK INFO IN THE SCHEDULE OR |
| | PROVIDE A NOTE TO INDICATE THE 3 SINKS WILL BE |
| | ACCESSIBLE TYPES. |
| | |
| | 4) FAILED. P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE |
| | RUNNING THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF |
| | PIPE MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND |
| | 107.2.1 WPB. SHEET P1 NOTES INDICATE PVC WASTE PIPING |
| | WHICH SHALL NOT BE INSTALLED IN PLENUM SPACES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |