2021-03-05 13:22:192ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20121350
 3/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS. THE REQUESTED COMMENT RESPONSE NARRATIVE
 WAS NOT PROVIDED.
  
 1) FAILED. P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL
 TO SEAL THE ANNULAR SPACE AROUND THE NEW SINK DRAIN
 PIPING PENETRATIONS- SECTION 315.1 FBC P AND SECTION
 714.4.1.2 FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN
 PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS- SECTION 107.2.1 WPB. FIRESTOPPING NOT
 PROVIDED.
  
 2) FAILED. SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN
 ONE, OF EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN
 COMPLIANCE WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE
 FOLLOWING DETAILS PER THE FBC ACC. REVISED SHEET A1.03
 DOES NOT INDICATE CLEAR FLOOR SPACES FOR THE NEW
 ACCESSIBLE SINKS IN THE BREAKROOM AND OFFICE.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SINKS- SECTIONS 212.3 AND 606.
 B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2,
 305, & 306.
 C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE
 THE FINISH FLOORS- 606.3.
  
 3) FAILED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE
 THAT INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING
 NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE
 SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH
 NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR
 WHAT THE REST OF THE SINKS IN THE ROOMS ARE TO BE USED
 FOR BECAUSE THEY ARE LISTED AS "BY OWNER". PLEASE
 CLARIFY THE USE OF THE SINKS AND NOTE THAT DEFERRED
 SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS MUST BE
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 CHARGE- SECTION 107.3.4.1 WPB. THREE NEW SINKS ARE
 BEING INSTALLED WHICH SHALL BE ACCESSIBLE. PLEASE
 PROVIDE THE REQUESTED SINK INFO IN THE SCHEDULE OR
 PROVIDE A NOTE TO INDICATE THE 3 SINKS WILL BE
 ACCESSIBLE TYPES.
  
 4) FAILED. P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE
 RUNNING THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF
 PIPE MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND
 107.2.1 WPB. SHEET P1 NOTES INDICATE PVC WASTE PIPING
 WHICH SHALL NOT BE INSTALLED IN PLENUM SPACES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER