| Date |
Text |
| 2021-01-22 16:22:03 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20121350 |
| | 1/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL TO SEAL |
| | THE ANNULAR SPACE AROUND THE NEW SINK DRAIN PIPING |
| | PENETRATIONS- SECTION 315.1 FBC P AND SECTION 714.4.1.2 |
| | FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN |
| | PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN |
| | ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED |
| | FLOOR TENDONS- SECTION 107.2.1 WPB. |
| | |
| | 2) SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN ONE, OF |
| | EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN COMPLIANCE |
| | WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE FOLLOWING |
| | DETAILS PER THE FBC ACC. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | NEW SINKS- SECTIONS 212.3 AND 606. |
| | |
| | B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2, |
| | 305, & 306. |
| | |
| | C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE |
| | THE FINISH FLOORS- 606.3. |
| | |
| | 3) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE THAT |
| | INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING |
| | NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE |
| | SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH |
| | NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR |
| | WHAT THE REST OF THE SINKS IN THE ROOMS ARE TO BE USED |
| | FOR BECAUSE THEY ARE LISTED AS "BY OWNER". PLEASE |
| | CLARIFY THE USE OF THE SINKS AND NOTE THAT DEFERRED |
| | SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS MUST BE |
| | REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN |
| | CHARGE- SECTION 107.3.4.1 WPB. |
| | |
| | 4) P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE RUNNING |
| | THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF PIPE |
| | MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |