| 2021-01-13 12:08:45 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 20121337 |
| | 1/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | NFPA 58-14 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED SURVEY AND RISER DRAWING INDICATE THE |
| | 250-GALLON LP TANK AS EXISTING HOWEVER ACCORDING TO WPB |
| | BUILDING DEPARTMENT RECORDS, PERMIT- 07041021 WHICH |
| | APPEARS TO HAVE INCLUDED THE TANK IS EXPIRED AND FINAL |
| | INSPECTION OF THE TANK WAS NEVER PERFORMED. BECAUSE |
| | YOUR PERMIT WILL INVOLVE CONNECTING THE NEW GAS LINE |
| | FROM THE TANK TO THE GENERATOR, THE NEW TANK MUST ALSO |
| | RECEIVE FINAL APPROVAL EITHER UNDER THIS NEW GAS |
| | PERMIT, OR UNDER THE PREVIOUS PERMIT THAT WAS ISSUED TO |
| | ABSOLUTE SEWER DRAIN CLEANING. PLEASE SEND AN EMAIL TO |
| | [email protected] FOR FURTHER ASSISTANCE. |
| | |
| | 2) THE GAS RISER DRAWING HAS AN INCOMPLETE UG LP TANK |
| | HOLD DOWN DETAIL HOWEVER THE RISER INDICATES THE TANK |
| | AS EXISTING. AGAIN, IT IS NOT CLEAR WHICH CONTRACTOR |
| | WILL BE ACCEPTING RESPONSIBILITY FOR THE TANK |
| | INSTALLATION, HOWEVER PLEASE NOTE THAT COMPLETE DETAILS |
| | FOR INSTALLATION OF THE TANK ARE REQUIRED FOR THE FINAL |
| | INSPECTION. PLEASE PROVIDE THE FOLLOWING ITEMS: |
| | |
| | A) MANUFACTURER'S SPECIFICATIONS FOR THE 250-GALLON UG |
| | LP TANK SHOWING THE TANK AND DOME HAVE BEEN DESIGNED, |
| | FABRICATED, TESTED AND MARKED (STAMPED) IN ACCORDANCE |
| | WITH THE REGULATIONS AS REQUIRED BY THE REGULATORY |
| | AGENCIES AND COMPLIANCE STANDARDS LISTED IN SECTION |
| | 5.2.1.1 NFPA 58. |
| | |
| | B) LP TANK INSTALLATION DETAILS SHOWING HOW THE TANK |
| | WILL BE ANCHORED TO PREVENT FLOTATION, COLLAPSE, OR |
| | LATERAL MOVEMENT- SECTION 6.6.1.6. PLEASE INCLUDE A |
| | FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE BURIAL |
| | DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, SIZES, |
| | AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND THE TYPE |
| | OF PROTECTIVE SLEEVES FOR THE CABLES OR STRAPS. |
| | |
| | C) CORROSION PROTECTION FOR THE TANK BY INSTALLATION OF |
| | A CATHODIC PROTECTION SYSTEM CONSISTING OF A |
| | SACRIFICIAL ANODE OR AN IMPRESSED CURRENT ANODE PER |
| | SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA 58. INDICATE THE |
| | TYPE OF PROTECTION AND HOW IT WILL BE TESTED- SECTION |
| | 6.17.1. |
| | |
| | 3) PLEASE MARK UP THE SURVEY DRAWING TO SHOW THE |
| | REQUIRED 10 FT. UG TANK CLEARANCE DISTANCES TO THE |
| | HOUSE AND ADJACENT PROPERTY LINES- TABLE 6.3.1.1 NFPA |
| | 58. PLEASE NOTE THAT IF THE TANKS ARE LESS TANK 10 FT. |
| | FROM THE DRIVEWAY, THE SHELLS FOR THE TANKS SHALL BE 18 |
| | IN. BELOW GRADE OR VEHICULAR BARRIER PROTECTION WILL BE |
| | REQUIRED- SECTIONS 6.6.6.1 (A). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |