| Plan Review Notes For Permit 20121326 |
| Permit Number |
20121326 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-07-06 13:26:01 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- PROVIDE PRODUCT APPROVAL FOR: | | | A)OVERHEAD GARAGE DOOR. | | | B)METAL ROOFING. | | | C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES. | | | D)EXTERIOR DOORS. | | | E)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR | | | DOORS. | | | F) WINDOW MULLIONS. AND SPECIFY MULLION SIZE. | | | | | | 2- ARCHITECT TO REVIEW/APPROVE ALL PRODUCT APPROVALS. | | | | | | 3-PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY | | | ARCHITECT OF RECORD). NOTE: TABLE R301.5 | | | FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE | | | "H". | | | | | | 4- PROVIDE BALCONY CABLE RAILINGS SHOP DRAWINGS | | | (REVIEWED BY ARCHITECT OF RECORD). |
|