| 2021-01-05 10:36:02 | 01/05/20 1ST REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING |
| | REFERENCED USED PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 101.4 REFERENCED CODES. ON PAGE A.0, IT REFERENCES THE |
| | BUIDING CODE, AND THESE PLANS ARE UNDER THE RESIDENTIAL |
| | CODE FOR THE DWELLING; PLEASE CLARIFY. |
| | |
| | 2. A SEPARATE PERMIT WILL BE REQUIRED FOR DEMOLITION |
| | AND CAP OFF PLUMBING PER THE WPB AMENDMENTS TO FBC SEC. |
| | 105.1. PLEASE PROVIDE A WATER SOURCE EITHER ON A FIRE |
| | HYDRANT OR WITH A BACKFLOW DEVICE THAT REQUIRES A |
| | PERMIT FOR THE DEMO WORK. |
| | |
| | 3. ON SHEET P.3, |
| | |
| | A. THE WASHING MACHINE IS SHOWN ON A STANDPIPE BELOW |
| | THE SLAB, WHICH EXCEEDS THE 42" MAX PER THE 2017 FBC |
| | SEC. R 2706.1.1 |
| | |
| | B. THE VENT IS ON A DRY VENT CONNECTING TO A HORIZONTAL |
| | DRAIN SHALL CONNECT ABOVE THE HORIZONTAL DRAIN PIPE'S |
| | CENTERLINE PER THE 2017 R 3104.3 VENT CONNECTION TO THE |
| | DRAINAGE SYSTEM. PLEASE SHOE CONNECTION ON A SANITARY |
| | FITTING TO P-TRAP. |
| | |
| | 4. THE UPSTAIRS DOUBLE LAV IS MISSING THE SECOND |
| | P-TRAP; PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. THE TANKLESS HEATER HAS PIPES NOT IN CONDITION SPACE |
| | AND NEEDS TO BE INSULATED WITH A MINIMUM R-3 PER THE |
| | 2017 FBC SEC. RE 403.5.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |