| 2021-01-05 11:10:48 | 01/05/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE A DIMENSION ON A HOUSE PLAN SHOWING |
| | THE TANK-LESS WATER HEATER'S LOCATION AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1' |
| | AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC R318.5. |
| | |
| | 3. PLEASE PROVIDE A SPECIFICATION THAT SHOWS LISTED AND |
| | LABELED IN ACCORDANCE WITH A SYMBOL OR OTHER |
| | IDENTIFYING MARK OF A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY, INSPECTION AGENCY, OR OTHER ORGANIZATION |
| | CONCERNED WITH PRODUCT EVALUATION THAT MAINTAINS |
| | PERIODIC INSPECTION OF THE PRODUCTION OF THE |
| | ABOVE-LABELED ITEMS AND WHOSE LABELING INDICATES EITHER |
| | THAT THE EQUIPMENT, MATERIAL OR PRODUCT MEETS |
| | IDENTIFIED STANDARDS OR HAS BEEN TESTED AND FOUND |
| | SUITABLE FOR A SPECIFIED PURPOSE. |
| | |
| | 4. PLEASE SHOW ALL REGULATORS AND UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| | G2421.2 OR 2017 FBC FG SEC 410.2. |
| | |
| | 5. NEED A HARD CAP FOR A FUTURE FIRE PIT; PLEASE SHOW |
| | ON GAS ISOMERIC G.1 APPLIANCE SHUTOFF 2017 FBC FG SEC. |
| | 409.5 OR 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |