| Plan Review Notes For Permit 20121297 |
| Permit Number |
20121297 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-26 13:35:12 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION MANUAL FOR THE NEW VACUUM PUMP. WPB AMEND. | | | TO FBC. SEC. 107.2.1. | | | 2) SHT. P1.1 - MEDICAL GAS NOTES - NOTE #2 (B) REFERS | | | TO THE TEXAS DEPT. OF STATE HEALTH SERVICES. REMOVE | | | THIS NOTE FROM THE PLANS SINCE IT IS NOT APPLICABLE. | | | 3) SHT. P1.1 - MEDICAL GAS & PLUMBING KEYNOTE # 3 | | | REFERS TO A NEW FLOOR SINK. SUBMIT A SANITARY RISER FOR | | | THIS NEW WORK.WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|