| 2022-09-29 16:16:34 | PERMIT 20121294 - UG POWER - 223 @ FERN ST. |
| | 1. THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO |
| | THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH |
| | THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED |
| | WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS |
| | BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS |
| | WELL AS WITH THIS PERMIT. |
| | |
| | |
| | PERMIT 19020382 - POLE - 223 @ FERN ST. |
| | 1. PLEASE PROVIDE SURVEY FOR ENTIRE SCOPE OF PROJECT, |
| | INCLUDING THE POWER ROUTE. STAFF WOULD LIKE TO VERIFY |
| | THAT ALL PROPOSED WORK AND CONNECTIONS ARE WITHIN THE |
| | RIGHT-OF-WAY. |
| | |
| | 2. PROPOSED POLE LOCATIONS OR BORE PITS SHOWN TO |
| | POTENTIALLY CONFLICT WITH EXISTING PRIVATE |
| | COMMUNICATIONS LINE, PLEASE PROVIDE THE NECESSARY |
| | UTILITY LETTERS GRANTING APPROVAL/NO OBJECTION OF THIS |
| | POLE LOCATION AND DEPTH, IF NO RESPONSE CAN BE OBTAINED |
| | FROM UTILITY PROVIDER, PLEASE PROVIDE PROOF OF |
| | COMMUNICATION AND A LETTER OF NO RESPONSE. |
| | |
| | 3. PLEASE PROVIDE PROOF THAT ADA CLEARANCE IS NOT |
| | IMPEDED IN THE SPACE BETWEEN BACK OF CURB AND THE FACE |
| | OF THE POLE, MUST MAINTAIN AT LEAST 36??? OF CLEARANCE. |
| | |
| | 4. PLEASE BE SURE THAT SITE PLAN PROVIDES FULL SCOPE OF |
| | WORK. |
| | |
| | 5. THE POLE STEALTH DESIGN AND COLOR MEETS CITY |
| | STANDARDS. |
| | |
| | |