2022-09-29 16:16:34PERMIT 20121294 - UG POWER - 223 @ FERN ST.
 1. THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
  
 PERMIT 19020382 - POLE - 223 @ FERN ST.
 1. PLEASE PROVIDE SURVEY FOR ENTIRE SCOPE OF PROJECT,
 INCLUDING THE POWER ROUTE. STAFF WOULD LIKE TO VERIFY
 THAT ALL PROPOSED WORK AND CONNECTIONS ARE WITHIN THE
 RIGHT-OF-WAY.
  
 2. PROPOSED POLE LOCATIONS OR BORE PITS SHOWN TO
 POTENTIALLY CONFLICT WITH EXISTING PRIVATE
 COMMUNICATIONS LINE, PLEASE PROVIDE THE NECESSARY
 UTILITY LETTERS GRANTING APPROVAL/NO OBJECTION OF THIS
 POLE LOCATION AND DEPTH, IF NO RESPONSE CAN BE OBTAINED
 FROM UTILITY PROVIDER, PLEASE PROVIDE PROOF OF
 COMMUNICATION AND A LETTER OF NO RESPONSE.
  
 3. PLEASE PROVIDE PROOF THAT ADA CLEARANCE IS NOT
 IMPEDED IN THE SPACE BETWEEN BACK OF CURB AND THE FACE
 OF THE POLE, MUST MAINTAIN AT LEAST 36??? OF CLEARANCE.
  
 4. PLEASE BE SURE THAT SITE PLAN PROVIDES FULL SCOPE OF
 WORK.
  
 5. THE POLE STEALTH DESIGN AND COLOR MEETS CITY
 STANDARDS.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 (561)822-1426 [email protected]
  