Plan Review Notes
Plan Review Notes For Permit 20121294
Permit Number 20121294
Review Stop Z
Sequence Number 4
Notes
Date Text
2022-03-21 16:28:27FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
 2) UPDATED COMMENT: THE POWER ROUTE PLAN SHEET P-1
 STATES THAT FPL WILL MAKE THE ELECTRICAL WIRE TAP FROM
 AN EXISTING POLE TO A PROPOSED HANDHOLE; HOWEVER, SHEET
 P-2 STATES THAT IT WILL COME FROM AN EXISTING
 TRANSFORMER. IF IT IS NOT FROM THE TRANSFORMER, YOU
 MUST SHOW WHICH POLE IS BEING USED SO THAT STAFF CAN
 VERIFY IMPACTS. IF YOU ARE USING THE TRANSFORMER, YOU
 MUST PROVIDE VERIFICATION THAT THERE IS A UTILITY
 EASEMENT THAT ALLOWS POWER SUPPLYING YOUR FACILITY TO
 CROSS CITY OWNED PROPERTY. IF THERE IS NO EASEMENT,
 POWER TO SUPPLY YOUR FACILITY MAY NOT CROSS CITY OWNED
 PROPERTY. THE BEST METHOD IS ON A SURVEY; HOWEVER,
 RECORDED DOCUMENTATION THAT CLEARLY IDENTIFIES THIS
 LOCATION IS ALSO ACCEPTABLE. NOTE: FPL STATING THEY
 HAVE AN EASEMENT, DOES NOT VERIFY THAT THEY HAVE AN
 EASEMENT. IF NO EASEMENT IS PRESENT THE UNDERGROUND
 ELECTRIC MUST COME FROM AN ALTERNATIVE LOCATION.
  
 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, SIDEWALK
 AND LANDSCAPE AREAS WILL NEED RESTORATION. PLEASE
 UPDATE THE NOTATIONS ACCORDINGLY.
  
 4) THE EASTERNMOST BORE PIT APPEARS TO CROSS THE
 RIGHT-OF-WAY LINE ONTO CITY PROPERTY, WHICH IS NOT
 PERMITTED. ALL WORK IS TO REMAIN IN THE RIGHT-OF-WAY
 UNLESS THERE IS A UTILITY EASEMENT PRESENT AND SHOWN ON
 THE SURVEY. THIS GOES FOR ALL THE INSTALLATIONS THAT
 ARE IMMEDIATELY ADJACENT TO THE RIGHT-OF-WAY LINE.
  
 5) REPEAT COMMENT: THE PLANS SHOW THE GAS LINE WITHIN
 2-FEET OF THE CAISSON AND THROUGH THE MAJORITY OF YOUR
 BORE PITS. IN ORDER TO VERIFY THAT THE INSTALLATION
 WILL NOT INTERFERE WITH THE EXISTING FACILITIES,
 PROVIDE A PUBLIC UTILITY LETTER OF NO OBJECTION FROM
 FPU REGARDING THE INSTALLATION.
  
 6) THIS POLE LOCATION IS APPROVED BY SPECIAL EVENTS.
  
 7) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7022 UMBRA GREY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  