Plan Review Notes
Plan Review Notes For Permit 20121293
Permit Number 20121293
Review Stop B
Sequence Number 2
Notes
Date Text
2021-05-04 13:07:38ANTENNA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE THE STRUCTURAL DETAILS AND
 CALCULATIONS FROM A DESIGN PROFESSIONAL FOR THE POLE
 AND MOUNTED ANTENNA SHOWING FOUNDATION AND ATTACHMENTS
 TO COMPLY WITH THE WIND LOADS PER FBC 1609
 2) WIND SPEED USED FOR DESIGN SHOULD BE 170MPH FOR A
 RISK CATEGORY II PER FBC WPB SECTION 120.