Plan Review Notes
Plan Review Notes For Permit 20121293
Permit Number 20121293
Review Stop E
Sequence Number 1
Notes
Date Text
2021-01-21 10:55:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) AIC RATING FOR SERVICE NOT SHOWN 110.9, 110.10
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
  
 2) NO GROUNDING DETAIL FOR ELECTRICAL SERVICE.
 250.4(A)(1)