Plan Review Notes
Plan Review Notes For Permit 20121276
Permit Number 20121276
Review Stop P
Sequence Number 1
Notes
Date Text
2021-02-12 15:06:191ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121276
 2/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C-1: THE PLUMBING FIXTURE CALCULATIONS DO NOT
 INCLUDE THE REQUIRED DRINKING FOUNTAIN FOR BUSINESS
 OCCUPANCIES ACCORDING TO TABLE 403.1 FBC P, AND THE
 PLANS DO NOT SHOW A DRINKING FOUNTAIN TO BE INSTALLED.
 PLEASE SEE SECTION 410.4 FOR ADDITIONAL INFORMATION.
  
 2) 1.0A, 1.2A, 4.0P: PLEASE IDENTIFY THE SINGLE USER
 TOILET ROOMS AS EITHER MALE OR FEMALE- SEE SECTION
 403.2(4) FBC P.
  
 3) 1.0A: PLEASE PROVIDE WALL AND FLOOR FINISH MATERIAL
 SPECIFICATIONS FOR THE NEW TOILET ROOM- REFER TO
 SECTION 310.3 FBC P, AND SECTIONS 1210.2.2 FBC B.
 PLEASE NOTE THAT PAINTED DRYWALL IS NOT IN COMPLIANCE
 WITH THE CODE SECTIONS.
  
 4) 1.0A: PLEASE PROVIDE THE NEW TOILET ROOM WIDTH AND
 LENGTH DIMENSIONS- SECTION 107.2.1 WPB AND 604.3.2 FBC
 ACC.
  
 5) 1.0A: PROVIDE THE DIAMETER OF THE TURNING CIRCLE-
 SECTIONS 603.2.1 AND 304 FBC ACC.
  
 6) 4.0P: SHOW THE VENT FOR THE MOP SINK IN THE SANITARY
 ISOMETRIC- SECTION 909 FBC P.
  
 7) 4.0P: PROVIDE AN INDIRECT WASTE DETAIL FOR THE MOP
 SINK- SECTION 802.1.1 FBC P.
  
 8) 4.0P: THE PLAN APPEARS TO SHOW VENT SYMBOLS FOR THE
 GREASE INTERCEPTOR, HOWEVER VENTS ARE NOT SHOWN IN THE
 SANITARY RISER. PLEASE REVIEW THE INSTALLATION MANUAL
 FOR THE INTERCEPTOR AND SHOW HOW IT WILL BE VENTED-
 SECTION 1003.3.4 FBC P.
  
 9) 4.0P: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTIONS
 416, 418, 420, 424, & 427 AND TABLE 604.5 FBC P.
  
 10) 4.0P: THE WATER RISER IS MISLABELED AS SANITARY
 RISER- PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 11) 4.0P: THE HAND SINK IS MISLABELED AS A LAV IN THE
 SANITARY RISER- PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 12) 4.0P: LABEL THE SINK IN THE KITCHEN ON THE RISER
 DRAWINGS. IT APPEARS THAT THE SINK IS BEING SUPPLIED
 WITH COLD WATER BUT NOT HOT WATER AS REQUIRED BY
 SECTION 607.1 FBC P.
  
 13) 4.0P: SHOW THE LOCATIONS WHERE THE MIXING VALVE
 WILL BE INSTALLED- SECTIONS 416.5 AND 607.1.2 FBC P.
  
 14) 4.0P: CORRECT THE HOT AND COLD LINE LABELS AT THE
 EXISTING LAV TO MATCH WITH THE PIPES IN THE RISER
 DRAWING- SECTION 107.2.1 WPB.
  
 15) 4.0P: SHOW LOCATIONS OF WATER HAMMER ARRESTORS AND
 PROVIDE A SPEC- SECTION 604.5 FBC P.
  
 16) 4.0P: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE AND
 SHOW THE HWR LINE IN THE DETAIL- TABLE C404.2 FBC EC
 AND SECTION 607.2.1.2 FBC P. VERIFY THAT THE WATER
 HEATER IS FACTORY EQUIPPED WITH A RECIRCULATION PUMP OR
 SHOW AN INDEPENDENT PUMP IS TO BE INSTALLED- SEE
 SECTION C404.5.1 FBC EC.
  
 17) 4.0P: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS- SECTION C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  