| 2021-02-12 15:06:19 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20121276 |
| | 2/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET C-1: THE PLUMBING FIXTURE CALCULATIONS DO NOT |
| | INCLUDE THE REQUIRED DRINKING FOUNTAIN FOR BUSINESS |
| | OCCUPANCIES ACCORDING TO TABLE 403.1 FBC P, AND THE |
| | PLANS DO NOT SHOW A DRINKING FOUNTAIN TO BE INSTALLED. |
| | PLEASE SEE SECTION 410.4 FOR ADDITIONAL INFORMATION. |
| | |
| | 2) 1.0A, 1.2A, 4.0P: PLEASE IDENTIFY THE SINGLE USER |
| | TOILET ROOMS AS EITHER MALE OR FEMALE- SEE SECTION |
| | 403.2(4) FBC P. |
| | |
| | 3) 1.0A: PLEASE PROVIDE WALL AND FLOOR FINISH MATERIAL |
| | SPECIFICATIONS FOR THE NEW TOILET ROOM- REFER TO |
| | SECTION 310.3 FBC P, AND SECTIONS 1210.2.2 FBC B. |
| | PLEASE NOTE THAT PAINTED DRYWALL IS NOT IN COMPLIANCE |
| | WITH THE CODE SECTIONS. |
| | |
| | 4) 1.0A: PLEASE PROVIDE THE NEW TOILET ROOM WIDTH AND |
| | LENGTH DIMENSIONS- SECTION 107.2.1 WPB AND 604.3.2 FBC |
| | ACC. |
| | |
| | 5) 1.0A: PROVIDE THE DIAMETER OF THE TURNING CIRCLE- |
| | SECTIONS 603.2.1 AND 304 FBC ACC. |
| | |
| | 6) 4.0P: SHOW THE VENT FOR THE MOP SINK IN THE SANITARY |
| | ISOMETRIC- SECTION 909 FBC P. |
| | |
| | 7) 4.0P: PROVIDE AN INDIRECT WASTE DETAIL FOR THE MOP |
| | SINK- SECTION 802.1.1 FBC P. |
| | |
| | 8) 4.0P: THE PLAN APPEARS TO SHOW VENT SYMBOLS FOR THE |
| | GREASE INTERCEPTOR, HOWEVER VENTS ARE NOT SHOWN IN THE |
| | SANITARY RISER. PLEASE REVIEW THE INSTALLATION MANUAL |
| | FOR THE INTERCEPTOR AND SHOW HOW IT WILL BE VENTED- |
| | SECTION 1003.3.4 FBC P. |
| | |
| | 9) 4.0P: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTIONS |
| | 416, 418, 420, 424, & 427 AND TABLE 604.5 FBC P. |
| | |
| | 10) 4.0P: THE WATER RISER IS MISLABELED AS SANITARY |
| | RISER- PLEASE CORRECT- SECTION 107.2.1 WPB. |
| | |
| | 11) 4.0P: THE HAND SINK IS MISLABELED AS A LAV IN THE |
| | SANITARY RISER- PLEASE CORRECT- SECTION 107.2.1 WPB. |
| | |
| | 12) 4.0P: LABEL THE SINK IN THE KITCHEN ON THE RISER |
| | DRAWINGS. IT APPEARS THAT THE SINK IS BEING SUPPLIED |
| | WITH COLD WATER BUT NOT HOT WATER AS REQUIRED BY |
| | SECTION 607.1 FBC P. |
| | |
| | 13) 4.0P: SHOW THE LOCATIONS WHERE THE MIXING VALVE |
| | WILL BE INSTALLED- SECTIONS 416.5 AND 607.1.2 FBC P. |
| | |
| | 14) 4.0P: CORRECT THE HOT AND COLD LINE LABELS AT THE |
| | EXISTING LAV TO MATCH WITH THE PIPES IN THE RISER |
| | DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 15) 4.0P: SHOW LOCATIONS OF WATER HAMMER ARRESTORS AND |
| | PROVIDE A SPEC- SECTION 604.5 FBC P. |
| | |
| | 16) 4.0P: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE AND |
| | SHOW THE HWR LINE IN THE DETAIL- TABLE C404.2 FBC EC |
| | AND SECTION 607.2.1.2 FBC P. VERIFY THAT THE WATER |
| | HEATER IS FACTORY EQUIPPED WITH A RECIRCULATION PUMP OR |
| | SHOW AN INDEPENDENT PUMP IS TO BE INSTALLED- SEE |
| | SECTION C404.5.1 FBC EC. |
| | |
| | 17) 4.0P: PROVIDE HOT WATER PIPE INSULATION |
| | SPECIFICATIONS- SECTION C403.2.10 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |