| 2021-02-09 11:18:19 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20121276 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE OUTDOOR CALCULATIONS BASED ON SECTION |
| | 403.3.1.1 AND TABLE 403.3.1.1 USING THE HEADING (FOOD |
| | AND BEVERAGE SERVICE) AND THEN (DINING ROOMS). THIS |
| | SHOULD BE BASED ON THIS TABLE AND NOT THE NUMBER OF |
| | PEOPLE THE DESIGNER HAS SHOWN. FBC M |
| | |
| | 2) PLEASE SHOW IN THE OUTDOOR AIR CALCULATIONS, THE |
| | REQUIRED COMBUSTION AIR CALCULATIONS FOR THE HOOD BASED |
| | ON SHEET 4.0P. FBC M 508.1.2 |
| | |
| | 3) PLEASE PROVIDE AN AIR BALANCE REPORT. FBC M 508.1.2 |
| | |
| | 4) PLEASE SHOW THE PLACEMENT OF THE KITCHEN EXHAUST AND |
| | MUA WILL MEET THE PROTECTIONS OF FBC M 304.11 AND 306.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |