| 2021-02-12 15:04:00 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20121276 |
| | 2/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4.0P: PLEASE UPDATE THE 5TH EDITION FBC- 2014 |
| | REFERENCE BY THE RISER DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 2) 4.0P: SHOW THE TANKLESS WATER HEATER IN THE RISER- |
| | SECTION 402.2 FBC FG. |
| | |
| | 3) 4.0P: SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | AND TOTAL LOAD- SECTIONS 402.2 AND 402.4.1. |
| | |
| | 4) 4.0P: SHOW REGULATORS AT THE WATER HEATER AND |
| | APPLIANCES- SECTION 410.1 & 410.2 FBC FG. |
| | |
| | 5) 4.0P: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER |
| | HEATER AND COOKING APPLIANCES AND SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS- SECTIONS 624.1 AND 623.1. |
| | |
| | 6) 4.0P: CONCERNING THE COMBUSTION AIR CALCULATIONS |
| | PLEASE REFER TO THE MECHANICAL REVIEW COMMENTS |
| | REQUESTING REVISED O/A CALCULATIONS IN ORDER TO VERIFY |
| | COMPLIANCE WILL BE MET- SECTION 304.9. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |