| Plan Review Notes For Permit 20121273 |
| Permit Number |
20121273 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-05 08:57:16 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | FBC B 1603.1.4, THE ENGINEER'S SIGNED/SEALED WIND LOAD | | | DATA IS REQUIRED INCLUDING: WIND SPEED, PRESSURES, | | | CATEGORY & EXPOSURE. | | | FBC B/WPB AMENDMENTS 107.2.1, THE FLOOR PLAN/SKETCH | | | NEEDS TO BEAR THE NAME & SIGNATURE OF THE INDIVIDUAL | | | RESPONSIBLE FOR IT (EXAMPLE: OWNER/CONTRACTOR). IF A | | | DESIGN PROFESSIONAL (ENGINEER OR ARCHITECT) IS | | | RESPONSIBLE, THE SIGNATURE AND SEAL IS REQUIRED. |
|