| Plan Review Notes For Permit 20121268 |
| Permit Number |
20121268 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-05 08:53:09 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC B 107.2.1. REVISE FLOOR PLANS/BUILDING FOOTPRINT | | | SHOWING LOCATION OF PROPOSED WINDOWS/DOORS TO BE | | | REPLACED AND PROVIDE DIMENSIONS OF EACH OPENING, | | | WINDOW/DOOR TYPE AND ROOM DESIGNATION. | | | 2. FBC B 1609. PROVIDE A COMPLETE SET OF SIGNED AND | | | SEALED DESIGN PRESSURE CALCULATIONS FOR HIGH | | | RISE/COMMERCIAL BUILDINGS BY A FLORIDA REGISTERED | | | DESIGN PROFESSIONAL. | | | 3. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA | | | 17-1226.13 IS A NON-IMPACT RATED FRENCH DOOR | | | W/SIDELITES. PROVIDE REQUIRED WINDBORNE DEBRIS | | | PROTECTION FOR EACH OPENING. (HURRICANE PROTECTION). | | | |
|