Plan Review Notes
Plan Review Notes For Permit 20121266
Permit Number 20121266
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-05 06:55:17PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2, PLEASE PROVIDE ADDITIONAL INFORMATION AS
 THE SIDELITE OPENINGS NEED TO BE PROTECTED WITH IMPACT
 RESISTANT COVERINGS. PROVIDE APPROVED ENGINEERING FOR
 WINDLOAD PRESSURE COMPLIANCE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved