| 2021-01-07 13:51:45 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT |
| | FROM UTILITY. |
| | |
| | AIC RATING OF SERVICE DISCONNECT AND PANEL |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| | |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| | FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| | NOT LESS THAN 10,000 AMPERES. (110.9) |
| | E3706.1PANELBOARD RATING. |
| | ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT |
| | OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR |
| | THE CALCULATED LOAD. (408.30) |
| | |
| | E3404.2INTERRUPTING RATING. |
| | |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| | |
| | PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC |
| | 110.3, 110.9; FBC RE E3606.4 |
| | |
| | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24 & FBC RE E3606.4 |
| | |
| | 2. DELETE-N/A |
| | |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |