1 |
|
| Notes |
| Date |
Text |
| 2021-01-15 15:09:01 | ADDING SECURITY GATES | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) GATES AND OVERHEAD ROLLUP DOOR ARE SUBJECT TO WIND | | | LOADS PLEASE SHOW ON THE DRAWINGS ALL ATTACHMENTS FOR | | | SUCH OR PROVIDE MIAMI DADE OR FLORIDA STATE PRODUCT | | | APPROVALS WITH WIND DESIGN PRESSURES THAT MEET OR | | | EXCEED THE REQUIRED WIND PRESSURES FOR THE SPECIFIC | | | OPENING. FBC 1609 | | | 2) DRAWINGS SHOW CODE USED FOR DESIGN AS 2017 FBC - | | | CODE IN EFFECT HAS CHANGED TO 2020 FBC - PLEASE REVISE | | | THE DRAWINGS TO REFLECT THE CODE IN EFFECT. | | | 3) PROVIDE SIGNAGE FOR THE FOLLOWING FIX - FBC 1011.7.4 | | | ENCLOSURES UNDER EXTERIOR STAIRWAYS. | | | THERE SHALL NOT BE ENCLOSED USABLE SPACE UNDER EXTERIOR | | | EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED | | | IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN | | | SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR | | | ANY PURPOSE. |
|