| 2021-01-12 09:02:30 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PROVISO ON PLAN SHEET E-1. SMOKE ALARMS SHALL COMPLY |
| | WITH R314.2.2. CT |
| | |
| | 1. PLAN SHEET E-1 STATES PANEL P LOCATED ON EAST WALL. |
| | SHOW LOCATION OF PANEL P ON PLAN. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. PROVIDE LOADS SERVED BY PANEL P. |
| | PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS |
| | FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR |
| | THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2. |
| | |
| | 3. AHU LOCATED IN ATTIC. PROVIDE SERVICE OUTLET AND |
| | LUMINAIRE. |
| | AHU IN ATTICS |
| | M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| | ACCORDANCE WITH CHAPTER 39. EXPOSED LAMPS SHALL BE |
| | PROTECTED FROM DAMAGE BY LOCATION OR LAMP GUARDS. |
| | |
| | E3901.12 HVAC OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | 4. LIST PANEL BOARD AIC RATING. |
| | E3706.1PANELBOARD RATING. |
| | ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT |
| | OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR |
| | THE CALCULATED LOAD. (408.30) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |