2021-01-13 20:24:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.VALUE LOW FOR AMOUNT OF WORK SHOWN. VALUE MUST
 INCLUDE ALL MATERIALS (INCLUDING CUSTOMER SUPPLIED) AND
 LABOR. FBC 109.3
  
 2. ALL FIRE ALARM WORK SHOWN (RELAYS, DUCT DETECTORS,
 ETC) WILL REQUIRE A SEPARATE FIRE ALARM PERMIT.
  
 END OF COMMENTS.
  