| Plan Review Notes For Permit 20121158 |
| Permit Number |
20121158 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-30 10:39:13 | THE PULL STATION IS NOT REQUIRED AT THAT EXIT PER NFPA | | | 101, CH 9 AND CAN BE REMOVED. | | | | | | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE | | | DETECTION OR | | | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM | | | SYSTEM IN | | | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN | | | ONE MANUAL | | | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY | | | HAVING | | | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE | | | ALARM SIGNAL. | | | | | | THERE ARE OTHER PULLS STATIONS THROUGHOUT THE | | | OCCUPANCY. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|