| 2021-02-11 15:53:37 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | PERMIT #20121151 |
| | |
| | 1- BASED ON THE WINDOW SCHEDULE ON SHEET A7.01 IT LOOKS |
| | LIKE THE SIZE OF SINGLE HUNG WINDOW SPECIFIED (3'-1" X |
| | 5'-0") SPECIFIED BY THE ARCHITECT DOESN'T COMPLY WITH |
| | THE MINIMUM CLEAR OPENING REQUIREMENTS OF SEC. R310.2.1 |
| | FBC-RESIDENTIAL. TYPICALLY A 60" HEIGHT IMPACT SINGLE |
| | HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR |
| | HEIGHT OPENING. PROVIDE MANUFACTURER'S CUT SHEETS |
| | SHOWING THAT THE SPECIFIED 37"X60" SINGLE HUNG WINDOW |
| | MEETS ALL THE EGRESS REQUIREMENTS, INCLUDING THE CLEAR |
| | OPENING HEIGHT AND TOTAL CLEAR OPENING OF 5.7 S.F. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 2- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | FBC-RESIDENTIAL. THIS PROPERTY IS LOCATED IN |
| | QUESTIONABLE SOILS. |
| | |
| | 3-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | |
| | 4-ENERGY CALCULATIONS: |
| | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S NAME AND BUILDER'S NAME. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B)CEILING TYPE ITEM #10(A) ON PAGE 1 OF 4 IS INCORRECT. |
| | ACCORDING TO PLANS THE ATTIC IS NOT VENTED. SEE PLANS |
| | AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C)PROJECT INFORMATION ON PAGE 2 OF 4 SPECIFIES 1 STORY |
| | BUILDING. THIS IS INCORRECT. THIS IS A TWO STORY |
| | BUILDING. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 IS INCORRECT. |
| | PLANS AND PRODUCT APPROVALS SUBMITTED ARE FOR ASPHALT |
| | SHINGLES NOT WOOD SHINGLES. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)ATTIC INFORMATION SPECIFIED ON PAGE 2 OF 4 IS |
| | INCORRECT. PLANS DON'T SPECIFY ATTIC VENTILATION. ATTIC |
| | IS DESIGNED AS UNVENTED. SEE PLANS AND REVISE ALL THE |
| | ATTIC VENTILATION AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | F)BUILDER TO SIGN THE ENERGY PERFORMANCE LEVEL (EPL) |
| | DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)WOOD ENTRY DOOR AS SPECIFIED ON PLANS AND DOOR |
| | SCHEDULE. |
| | |
| | B)HARDIE BOARD SIDING AS SPECIFIED ON PLANS. |
| | |
| | 6-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- PLANS SHOW A REAR PATIO WITH A ROOF PITCH OF 3:12. |
| | DESIGNER OF RECORD TO SPECIFY DOUBLE UNDERLAYMENT AS |
| | REQUIRED BY SEC. R905.2.2 FBC-RESIDENTIAL. |
| | NOTE: SAME COMMENT APPLIES TO MAIN ROOF OVERHANG. IT |
| | ALSO SHOWS A 3:12 PITCH. |
| | |
| | 8- PROVISO: |
| | A)HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL: PROVIDE |
| | SHOP DRAWINGS REVIEWED BY THE DESIGN PROFESSIONAL OF |
| | RECORD PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. |
| | TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1 |
| | FBC-RESIDENTIAL. |
| | |
| | B)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | PROPOSED FACTORY BUILT FIREPLACE SHOWING COMPLIANCE |
| | WITH SEC. R1004 FBC-RESIDENTIAL AND FACTORY BUILT |
| | CHIMNEY SHOWING COMPLIANCE WITH SEC. R1005 |
| | FBC-RESIDENTIAL |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE IN WRITING PRIOR |
| | TO SUBMITTAL TO THIS OFFICE. |
| | |
| | C) ICYNENE FOAM INSULATION ESR-1826 REPORT SUBMITTED |
| | STATES ON THE COVER PAGE THAT THIS REPORT IS SUBJECT TO |
| | RENEWAL ON 02/2018. PROVIDE CURRENT REPORT. SEC. |
| | 107.2.1 CITY AMENDMENTS. SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |