Plan Review Notes
Plan Review Notes For Permit 20121149
Permit Number 20121149
Review Stop B
Sequence Number 1
Notes
Date Text
2021-02-09 15:53:13NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 PERMIT #20121149
  
 1-ENERGY CALCULATIONS:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 7TH EDITION
 (2020).
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. OWNER'S NAME DOESN'T MATCH OWNER'S NAME SHOWN ON
 THE PERMIT APPLICATION. REVISE AS REQUIRED. AND,
 PROVIDE THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C)TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4 IS INCORRECT.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D)REVISE WINDOWS OVERHANG SEPARATION SHOWN ON PAGE 3 OF
 4 TO MATCH EXTERIOR ELEVATIONS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D) BUILDER TO SIGN THE ENERGY PERFORMANCE LEVEL (EPL)
 DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- PROPOSED LAYOUT SHOWN ON THE SURVEY SUBMITTED AND
 PROPOSED LAYOUT SHOWN ON THE ARCHITECTURAL SITE PLAN
 SHEET SP-1 DON'T MATCH. REVISE ALL THE SETBACKS AS
 REQUIRED TO MATCH. ALSO, LOCATION OF THE DRIVEWAY
 DOESN'T MATCH EITHER. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
 NOTE: ARCHITECTURAL SITE PLAN IS THE ONE THAT WAS
 APPROVED BY ZONING. ANY CHANGES WILL NEED TO BE RE-SENT
 TO ZONING FOR REVIEW/APPROVAL.
  
 3- DRAINAGE PLAN DRAWING C-1 SUBMITTED:
 A) COORDINATE WITH ITEM #2 ABOVE TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)BASED ON THE PROPOSED GRADE ELEVATIONS AND THE
 EXISTING ADJACENT PROPERTIES GRADE ELEVATIONS SECTION
 B, SECTION C AND SECTION D DON'T SHOW HOW THE WATER IS
 GOING TO BE RETAINED WITHIN THE LOT. ALL THESE SECTIONS
 SHOW WATER RUNNING TOWARDS ADJACENT PROPERTIES. REVISE
 AS REQUIRED CLEARLY DEPICTING HOW RETAINING THE WATER
 WITHIN THE LOT AS REQUIRED BY SEC. 110.9 CITY
 AMENDMENTS. SEC. 107.2.5 CITY AMENDMENTS AND SECTION
 R401.3 FBC-RESIDENTIAL,
  
 C) OWNER INFORMATION, PARCEL ID INFORMATION, IS
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D)JAMES MILLS, P.E. DIGITAL SIGNATURE HAS A SELF
 CERTIFIED DIGITAL SIGNATURE. FBPE DOES NOT ALLOW USE OF
 SELF CERTIFIED SIGNATURES. PLEASE OBTAIN A DIGITAL
 SIGNATURE ISSUED BY A CERTIFICATE AUTHORITY (OFTEN
 CALLED AS 3RD PARTY CERTIFICATION).
 FAC 61G15-23.004
  
 E) DRAINAGE PLAN SHOULD BE UPLOADED TO PROJECTDOX IN
 THE "DRAWINGS" FOLDER NO IN THE "SUPPORTING DOCUMENTS"
 FOLDER AS REQUIRED BY CITY GUIDELINES FOR DIGITAL PLAN
 REVIEW. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE COORDINATE WITH PERMIT LIBRARIAN TO MOVE
 THIS DRAWING TO THE DRAWINGS FOLDER SO THEY CAN BE
 VERSIONED WITH THE REVISED DRAWING.
  
 4- SURVEY SUBMITTED:
 A)SURVEY SHOULD BE UPLOADED TO PROJECTDOX IN THE
 "DRAWINGS" FOLDER NO IN THE "SUPPORTING DOCUMENTS"
 FOLDER AS REQUIRED BY CITY GUIDELINES FOR DIGITAL PLAN
 REVIEW. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE COORDINATE WITH PERMIT LIBRARIAN TO MOVE
 THIS DRAWING TO THE DRAWINGS FOLDER.
  
 B) CLARIFY WHY THE SURVEY SUBMITTED WAS NAMED "SITE
 PLAN-DRIVEWAY DIST SITE PLAN 515 LILAC" INSTEAD OF
 SURVEY OR BOUNDARY SURVEY (CONSTRUCTION LAYOUT) AS
 DESCRIBED BY THE SURVEYOR ON SURVEY SUBMITTED.
 CLARIFY/REVISE AS REQUIRED. PROPER NAMING OF THE
 DRAWINGS/DOCUMENTS SUBMITTED HELPS FOR PROPER RECORDS
 RETENTION MANAGEMENT. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 5- EXTERIOR DOORS:
 TYPE OF EXTERIOR DOORS TO BE INSTALLED IS NOT CLEAR.
 CLARIFY IF USING THERMATRU FIBERGLASS DOORS OR ALUMINUM
 FRENCH DOORS. BOTH PRODUCT APPROVALS WERE SUBMITTED.
 EITHER ONE CAN BE USED, BUT NEED TO CONFIRM WHICH ONE
 IS GOING TO BE INSTALLED. IF USING THE ALUMINUM FRENCH
 DOORS, THEN THE ENERGY CALCULATIONS NEED TO BE REVISED
 ACCORDINGLY. REVISE/CLARIFY AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: ALSO CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 OVERHEAD GARAGE DOOR. THERE IS NO GARAGE IN THIS HOUSE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY