2021-02-09 16:58:24BUILDING AUDIT COMMENTS
 NEW SINGLE FAMILY RESIDENCE (R3).
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 PERMIT #20121148
  
 1-ENERGY CALCULATIONS:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 7TH EDITION
 (2020).
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. OWNER'S NAME DOESN'T MATCH OWNER'S NAME SHOWN ON
 THE PERMIT APPLICATION. REVISE AS REQUIRED. AND,
 PROVIDE THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) BUILDER TO SIGN THE ENERGY PERFORMANCE LEVEL (EPL)
 DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- PROPOSED LAYOUT SHOWN ON THE SURVEY SUBMITTED AND
 PROPOSED LAYOUT SHOWN ON THE ARCHITECTURAL SITE PLAN
 SHEET SP-1 DON'T MATCH. REVISE ALL THE SETBACKS AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: ARCHITECTURAL SITE PLAN IS THE ONE THAT WAS
 APPROVED BY ZONING. ANY CHANGES WILL NEED TO BE RE-SENT
 TO ZONING FOR REVIEW/APPROVAL.
  
 3- DRAINAGE PLAN DRAWING C-1 SUBMITTED:
 A) COORDINATE WITH ITEM #2 ABOVE TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) OWNER INFORMATION, ZONING INFORMATION (38 -LAKE
 WORTH BEACH?) IS INCORRECT. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) DRAINAGE PLAN SHOULD BE UPLOADED TO PROJECTDOX IN
 THE "DRAWINGS" FOLDER NO IN THE "SUPPORTING DOCUMENTS"
 FOLDER AS REQUIRED BY CITY GUIDELINES FOR DIGITAL PLAN
 REVIEW. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE COORDINATE WITH PERMIT LIBRARIAN TO MOVE
 THIS DRAWING TO THE DRAWINGS FOLDER SO THEY CAN BE
 VERSIONED WITH THE REVISED DRAWING.
  
 4- SURVEY SUBMITTED:
 A)SURVEY SHOULD BE UPLOADED TO PROJECTDOX IN THE
 "DRAWINGS" FOLDER NO IN THE "SUPPORTING DOCUMENTS"
 FOLDER AS REQUIRED BY CITY GUIDELINES FOR DIGITAL PLAN
 REVIEW. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE COORDINATE WITH PERMIT LIBRARIAN TO MOVE
 THIS DRAWING TO THE DRAWINGS FOLDER.
  
 B) CLARIFY WHY THE SURVEY SUBMITTED WAS NAMED "LILIAC
 COURT-SITE PLAN-DRIVEWAY DIST SITE PLAN" INSTEAD OF
 SURVEY OR BOUNDARY SURVEY (CONSTRUCTION LAYOUT) AS
 DESCRIBED BY THE SURVEYOR ON SURVEY SUBMITTED.
 CLARIFY/REVISE AS REQUIRED. PROPER NAMING OF THE
 DRAWINGS/DOCUMENTS SUBMITTED HELPS FOR PROPER RECORDS
 RETENTION MANAGEMENT. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 5- TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES 10"
 FOOTING DEPTH. ACCORDING TO SEC. R403.1.4
 FBC-RESIDENTIAL EXTERIOR FOOTING REQUIRES 12" MIN.
 DEPTH. REVISE AS REQUIRED.
  
 6- ROOF FRAMING PLAN ON SHEET S-2:
 A) MISSING SPECIFICATIONS FOR CONNECTORS AT THE HIP
 ENDS ON THE SOUTH SIDE. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) CLARIFY WHY THE TRUSS CONNECTOR SPECIFIED FOR THE
 HIP GIRDER TRUSS ON THE SOUTH SIDE IS THE SAME
 CONNECTOR SPECIFIED FOR ALL OTHER ROOF TRUSSES.
 TYPICALLY, HIP GIRDER TRUSSES SUPPORT HIGHER UPLIFT
 LOADS. HIP GIRDER TRUSS ON THE NORTH SIDE OF THE SAME
 ROOF FRAMING PLAN SPECIFY A DIFFERENT CONNECTOR.
 CLARIFY REVISE AS REQUIRED. SEC. 107.2.1.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- EXTERIOR DOORS:
 TYPE OF EXTERIOR DOORS TO BE INSTALLED IS NOT CLEAR.
 CLARIFY IF USING THERMATRU FIBERGLASS DOORS OR ALUMINUM
 FRENCH DOORS. BOTH PRODUCT APPROVALS WERE SUBMITTED.
 EITHER ONE CAN BE USED, BUT NEED TO CONFIRM WHICH ONE
 IS GOING TO BE INSTALLED. IF USING THE ALUMINUM FRENCH
 DOORS, THEN THE ENERGY CALCULATIONS NEED TO BE REVISED
 ACCORDINGLY. REVISE/CLARIFY AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: ALSO CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 OVERHEAD GARAGE DOOR. THERE IS NO GARAGE IN THIS HOUSE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,