| 2021-04-29 17:24:47 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20121129 |
| | 4/29/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW ARE LISTED |
| | BELOW WITH NOTES ADDED IN CAPS. |
| | |
| | 1) FAILED. P0.1: PROVIDE PLUMBING FIXTURE CALCULATIONS |
| | IN COMPLIANCE WITH TABLE 403.3 FBC P. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | NUMBER OF REQUIRED FIXTURES. PLEASE NOTE THAT A SERVICE |
| | SINK IS A REQUIRED FOR MERCANTILE AND STORAGE |
| | OCCUPANCIES. REVISE THE PLANS ACCORDINGLY. THE COMMENT |
| | RESPONSE NARRATIVE STATES THE FIXTURES CALCULATIONS ARE |
| | ON A4.0.1 HOWEVER THEY ARE NOT SHOWN THERE. |
| | |
| | 2) FAILED. SHEETS P0.1, P2.1 & P5.1: A GREASE |
| | INTERCEPTOR IS REQUIRED IN ACCORDANCE WITH 1003.3.1 FBC |
| | P TO RECEIVE THE DRAINAGE FROM THE 3-COMPARTMENT SINK |
| | (SK-3) AND THE SK SINKS. THE LARGE SK SINK APPEARS TO |
| | BE FOR FOOD PREP OR POT OR DISHWASHING WHICH REQUIRES |
| | AN INDIRECT WASTE PIPE. SIZING CALCULATIONS FOR THE |
| | INTERCEPTORS HAVE NOT BEEN PROVIDED. SEE COMMENT 4 |
| | BELOW CONCERNING PLUMBING PIPING INSTALLATION AND |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| | |
| | 4) FAILED. P0.1: REFER TO SECTION 802.1 FBC P AND |
| | PROVIDE AN INDIRECT WASTE DETAIL FOR SK-3 AND THE LARGE |
| | SK SINK. INDIRECT WASTE DETAIL NOT PROVIDED. PLEASE |
| | NOTE THAT THE PLUMBING PLANS ARE SHOWING A DIRECT |
| | CONNECTION FROM THE 3-BAY SINK AND PREP SINK TO THE |
| | INTERCEPTORS WHICH IS NOT IN COMPLIANCE WITH SECTION |
| | 802.1. PLEASE PROVIDE GREASE INTERCEPTOR PLUMBING |
| | DIAGRAMS FROM THE MANUFACTURER TO VERIFY COMPLIANCE- |
| | SECTION 1003.3.5. |
| | |
| | 6) FAILED. P2.1 & P5.1: INDICATE HOW TRAP SEALS WILL BE |
| | PROVIDED FOR THE TRENCH DRAINS- SECTIONS 901.2 & |
| | 1002.4.1 FBC P. TRAPS HAVE BEEN ADDED BUT NOT TRAP |
| | SEALS- |
| | 1002.4.1 TRAP SEAL PROTECTION. TRAP SEALS OF EMERGENCY |
| | FLOOR DRAIN TRAPS AND TRAP SEALS SUBJECT TO EVAPORATION |
| | SHALL BE PROTECTED BY ONE OF THE METHODS IN SECTIONS |
| | 1002.4.1.1 THROUGH 1002.4.1.4. |
| | 1002.4.1.1 POTABLE WATER-SUPPLIED TRAP SEAL PRIMER |
| | VALVE. A POTABLE WATER-SUPPLIED TRAP SEAL PRIMER VALVE |
| | SHALL SUPPLY WATER TO THE TRAP. WATER-SUPPLIED TRAP |
| | SEAL PRIMER VALVES SHALL CONFORM TO ASSE 1018. THE |
| | DISCHARGE PIPE FROM THE TRAP SEAL PRIMER VALVE SHALL |
| | CONNECT TO THE TRAP ABOVE THE TRAP SEAL ON THE INLET |
| | SIDE OF THE TRAP. |
| | |
| | 8) FAILED. A1.1.1, P2.1 & P5.1: THE FLOOR PLAN SHOWS AN |
| | ICE MACHINE WITH NO WASTE RECEPTOR TO RECEIVE THE |
| | DRAINAGE FROM THE ICE AND THE CONDENSATION. PLEASE |
| | INDICATE HOW THE DRAINAGE WILL BE DISCHARGED TO AN |
| | APPROVED LOCATION- SECTION 314.2 FBC P. THE RESPONSE |
| | NARRATIVE STATES THAT THE ICE MACHINE HAS BEEN REMOVED |
| | HOWEVER SHEET A1.1.1 IS SHOWING THE ICE MACHINE AND |
| | ALS1.1 SHOWS A LOBSTER TANK. THE PLANS ARE IN CONFLICT. |
| | |
| | 9) PLEASE PROVIDE THE WATER HEATER COMPLAINCE DATA ON |
| | THE ENERGY EFFICIENCY REPORT- TABLE C404.2 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |