| 2021-04-07 13:53:59 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20121129 |
| | 4/7/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST. |
| | NO CORRECTED PLANS OR NARRATIVE RESPONSES WERE |
| | SUBMITTED. |
| | |
| | 1) SHEET P5.1 GAS RISER: |
| | A) SHOW THE METER AND THE GAS DELIVERY PRESSURE AT THE |
| | METER- SECTION 402.1 & 401.2 FBC FG. |
| | B) INDICATE THE TYPE OF GAS PIPING- SECTION 402.3 FBC |
| | FG. |
| | C) SHOW THE LOCATION OF THE REGULATOR AT THE WATER |
| | HEATER AND INDICATE THE REQUIRED GAS INPUT PRESSURE- |
| | SECTION 410.1 & 410.2 FBC FG. |
| | |
| | 2) P5.1: PLEASE UPDATE THE FBC-2004 FUEL GAS CODE |
| | REFERENCE TO THE CODE IN FORCE FOR THIS PERMIT- 2017- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) P0.1 & P5.1: PROVIDE A WATER HEATER EQUIPMENT |
| | SCHEDULE ON THE PLAN AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTION G2448.1 FBC FG AND TABLE C404.2 |
| | FBC EC. |
| | |
| | 4) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1 |
| | FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |