Plan Review Notes
Plan Review Notes For Permit 20121129
Permit Number 20121129
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-20 14:30:121ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121129
 1/20/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P0.1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 REQUIRED FIXTURES. PLEASE NOTE THAT A SERVICE SINK IS A
 REQUIRED FOR MERCANTILE AND STORAGE OCCUPANCIES. REVISE
 THE PLANS ACCORDINGLY.
  
 2) SHEETS P0.1, P2.1 & P5.1: A GREASE INTERCEPTOR IS
 REQUIRED IN ACCORDANCE WITH 1003.3.1 FBC P TO RECEIVE
 THE DRAINAGE FROM THE 3-COMPARTMENT SINK (SK-3) AND THE
 SK SINKS. THE LARGE SK SINK APPEARS TO BE FOR FOOD PREP
 OR POT OR DISHWASHING WHICH REQUIRES AN INDIRECT WASTE
 PIPE.
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR.
  
 3) P0.1, P2.1 & P5.1: THE PLANS DO NOT MAKE CLEAR THE
 NEED FOR THE LARGE TRENCH DRAINS AND WHAT DRAINAGE THEY
 WILL RECEIVE. PLEASE NOTE THE REQUIREMENT IN COMMENT #1
 FOR THAT DRAINAGE TO BE DISCHARGED INTO A GREASE
 INTERCEPTOR AND PLEASE CLARIFY- SECTION 1003.3.1 AND
 SECTION 107.2.1 WPB.
  
 4) P0.1: REFER TO SECTION 802.1 AND PROVIDE AN INDIRECT
 WASTE DETAIL FOR SK-3 AND THE LARGE SK SINK.
  
 5) P0.1, P2.1 & P5.1: THE TRENCH DRAIN FIXTURE
 SPECIFICATIONS INDICATE THE DRAINS ARE FOR CORROSIVE OR
 ACID WASTE APPLICATIONS. PLEASE CLARIFY WHAT DRAINAGE
 THEY WILL RECEIVE AND NOTE SECTION 803.1 REQUIRES
 CORROSIVE LIQUIDS, SPENT ACIDS, OR OTHER HARMFUL
 CHEMICALS TO BE NEUTRALIZED OR DILUTED BY A DEVICE
 BEFORE DISCHARGING INTO THE PLUMBING SYSTEM.
  
 6) P2.1 & P5.1: INDICATE HOW TRAP SEALS WILL BE
 PROVIDED FOR THE TRENCH DRAINS- SECTIONS 901.2 &
 1002.4.1 FBC P.
  
 7) P2.1 & P5.1: PROVIDE VENTS FOR THE TWO LARGE TRENCH
 DRAINS- SECTION 901.2.1 FBC P.
  
 8) A1.1.1, P2.1 & P5.1: THE FLOOR PLAN SHOWS AN ICE
 MACHINE WITH NO WASTE RECEPTOR TO RECEIVE THE DRAINAGE
 FROM THE ICE AND THE CONDENSATION. PLEASE INDICATE HOW
 THE DRAINAGE WILL BE DISCHARGED TO AN APPROVED
 LOCATION- SECTION 314.2 FBC P.
 9) AD.1.1: PROVIDE A SLAB REPAIR DETAIL- SECTION
 107.2.1 WPB.
  
 10) P0.1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE ON
 THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION G2448.1 FBC FG AND TABLE C404.2 FBC EC.
  
 11) A4.01: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
  
 A) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 B) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2
 C) DRINKING FOUNTAIN KNEE AND TOE CLEARANCES, SPOUT
 HEIGHT FOR THE HI FOUNTAIN- SECTIONS 606.2 & 306. SHOW
 HOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
  
 12) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  