| Date |
Text |
| 2020-12-29 15:25:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET ALS 1.1 - THERE IS AN INDICATION UNDER THE |
| | SCOPE OF WORK OF 3,033 SQ FT. THERE IS ALSO INDICATIONS |
| | OF A MIXED OCCUPANCY/ STORAGE - MERCANTILE. |
| | |
| | THERE ARE NO INDICATIONS OF SEPARATION MAKING IT |
| | MERCANTILE OCCUPANCY - CLASS B, REQUIREING TWO EXITS . |
| | |
| | 36.1.2.2 SUBCLASSIFICATION OF OCCUPANCY. |
| | 36.1.2.2.1 MERCANTILE OCCUPANCIES SHALL BE |
| | SUBCLASSIFIED AS |
| | FOLLOWS: |
| | (1) CLASS A, ALL MERCANTILE OCCUPANCIES HAVING AN |
| | AGGREGATE |
| | GROSS AREA OF MORE THAN 30,000 FT2 (2800 M) OR |
| | OCCUPYING |
| | MORE THAN THREE STORIES FOR SALES PURPOSES |
| | (2) CLASS B, AS FOLLOWS: |
| | (A) ALL MERCANTILE OCCUPANCIES OF MORE THAN 3000 FT2 |
| | (280 |
| | M2), BUT NOT MORE THAN 30,000 FT2 (2800 M2), AGGREGATE |
| | GROSS AREA AND OCCUPYING NOT MORE THAN THREE STORIES |
| | FOR |
| | SALES PURPOSES |
| | (B) ALL MERCANTILE OCCUPANCIES OF NOT MORE THAN 3000 |
| | FT2 |
| | (280 M3) GROSS AREA AND OCCUPYING TWO OR THREE STORIES |
| | FOR SALES PURPOSES |
| | (3) CLASS C, ALL MERCANTILE OCCUPANCIES OF NOT MORE |
| | THAN 3000 |
| | FT2 (280 M2) GROSS AREA AND USED FOR SALES PURPOSES |
| | OCCUPYING ONE STORY ONLY |
| | |
| | THERE ARE ALSO INDICATIONS OF ONE ONLY EXIT FROM EACH |
| | SPACE - STORAGE & MERCANTILE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OF THE OCCUOANCY |
| | CLASSIFICATION PER NFPA 101, CH 36 AND CH 6 |
| | |
| | |
| | |
| | 1A) PROVIDE THE APPLICABLE NUMBER OF EXITS PER THAT |
| | CLASSIFICATION. |
| | |
| | 36.2 MEANS OF EGRESS REQUIREMENTS. |
| | 36.2.1 GENERAL. |
| | 36.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE |
| | WITH CHAPTER |
| | 7 AND THIS CHAPTER. |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, |
| | STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND |
| | 37, |
| | RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR |
| | OTHER ROOMS OR |
| | SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH |
| | ROOMS OR |
| | SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, |
| | 19, 22, OR 23. |
| | |
| | ENSURE COMPLIANCE . |
| | |
| | 2) PLEASE PROVIDE THE STORAGE TYPE INCLUDING RACKS |
| | LOCATION, RACK HEIGHTS, COMMODITY STORED, PALLETS, |
| | WRAPPING, ETC. |
| | |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |