2020-12-29 15:25:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS 1.1 - THERE IS AN INDICATION UNDER THE
 SCOPE OF WORK OF 3,033 SQ FT. THERE IS ALSO INDICATIONS
 OF A MIXED OCCUPANCY/ STORAGE - MERCANTILE.
  
 THERE ARE NO INDICATIONS OF SEPARATION MAKING IT
 MERCANTILE OCCUPANCY - CLASS B, REQUIREING TWO EXITS .
  
 36.1.2.2 SUBCLASSIFICATION OF OCCUPANCY.
 36.1.2.2.1 MERCANTILE OCCUPANCIES SHALL BE
 SUBCLASSIFIED AS
 FOLLOWS:
 (1) CLASS A, ALL MERCANTILE OCCUPANCIES HAVING AN
 AGGREGATE
 GROSS AREA OF MORE THAN 30,000 FT2 (2800 M) OR
 OCCUPYING
 MORE THAN THREE STORIES FOR SALES PURPOSES
 (2) CLASS B, AS FOLLOWS:
 (A) ALL MERCANTILE OCCUPANCIES OF MORE THAN 3000 FT2
 (280
 M2), BUT NOT MORE THAN 30,000 FT2 (2800 M2), AGGREGATE
 GROSS AREA AND OCCUPYING NOT MORE THAN THREE STORIES
 FOR
 SALES PURPOSES
 (B) ALL MERCANTILE OCCUPANCIES OF NOT MORE THAN 3000
 FT2
 (280 M3) GROSS AREA AND OCCUPYING TWO OR THREE STORIES
 FOR SALES PURPOSES
 (3) CLASS C, ALL MERCANTILE OCCUPANCIES OF NOT MORE
 THAN 3000
 FT2 (280 M2) GROSS AREA AND USED FOR SALES PURPOSES
 OCCUPYING ONE STORY ONLY
  
 THERE ARE ALSO INDICATIONS OF ONE ONLY EXIT FROM EACH
 SPACE - STORAGE & MERCANTILE.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF THE OCCUOANCY
 CLASSIFICATION PER NFPA 101, CH 36 AND CH 6
  
  
  
 1A) PROVIDE THE APPLICABLE NUMBER OF EXITS PER THAT
 CLASSIFICATION.
  
 36.2 MEANS OF EGRESS REQUIREMENTS.
 36.2.1 GENERAL.
 36.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER
 7 AND THIS CHAPTER.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 ENSURE COMPLIANCE .
  
 2) PLEASE PROVIDE THE STORAGE TYPE INCLUDING RACKS
 LOCATION, RACK HEIGHTS, COMMODITY STORED, PALLETS,
 WRAPPING, ETC.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  