| 2020-12-30 13:27:10 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2014 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. NON-IMPACT RATED DOOR FL22513 WILL REQUIRED OPENING | | | PROTECTIVE DEVISES OR ASSEMBLIES. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE WIND DESIGN PRESSURES FOR EACH OPENING. | | | R301.2.1 WIND DESIGN CRITERIA. | | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | | FROM FIGURE R301.2(4). | | | | | | 3. PROVIDE PRODUCT APPROVALS FOR SHUTTERS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | NOTICE: A CITY OF WEST PALM BEACH SHUTTER SCHEDULE IS | | | AVAILABLE UPON REQUEST. | | | |
|