| Plan Review Notes For Permit 20121105 |
| Permit Number |
20121105 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-23 09:33:31 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEER'S DRAWINGS SPECIFY ASCE7-10 WHICH IS | | | THE STANDARD REFERENCED IN THE FBC SIXTH EDITION | | | (2017). THE CURRENT CODE IS THE FBC SEVENTH EDITION | | | (2020) WHICH REFERENCES ASCE7-16 AND WENT INTO EFFECT | | | ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR | | | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND | | | REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE7-16. FS | | | CHAPTER 553 | | | | | | 2) THE ENGINEERING DOCUMENT REQUIRES THE AWNING COVERS | | | TO BE REMOVED WHEN WINDS ARE EXPECTED TO EXCEED 75 MPH. | | | SUBMIT TWO SETS OF DETAILED AWNING REMOVAL INSTRUCTIONS | | | WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW THIS IS DONE IN | | | TERMS THAT A LAYMAN WILL UNDERSTAND. THESE INSTRUCTIONS | | | ARE TO BE PROVIDED TO THE PROPERTY OWNER, OWNER'S | | | REPRESENTATIVE OR LESSEE. FBC 107.2.1 | | | |
|