| 2021-11-02 06:21:12 | 11/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) SHT. A-1.3.01 - THE SINK IN ONE OF THE TREATMENT |
| | ROOMS AND ONE OF THE COUPLE'S SUITES AT THE SPA SHALL |
| | COMPLY WITH FBC-ACCESSIBILITY SECS. 212.3, 606.1. THE |
| | RESPONSE NARRATIVE REFERS TO STAFFING BY "ABLE-BODIED" |
| | EMPLOYEES, WHICH HAS NOTHING TO DO WITH THE HEIGHT OF |
| | THE SINKS IN THESE ROOMS. SHOW COMPLIANCE ON THE PLANS |
| | WITH THE ACCESSIBILITY REQUIREMENTS FOR THE SINKS?2ND |
| | REQUEST. |
| | |
| | I WENT TO LOOK FOR SHEET D.2.4.02, AND IT IS MISSING. |
| | THE INDEX SAYS IT HAS A LOT MORE D THAN UPLOADED, SO |
| | THEY NEED TO BE CHECKED WITH PROJECT DOX TO SEE WHAT IS |
| | MISSING. |
| | |
| | 2. DONE. |
| | |
| | 3) SHT. P-1.1.00 - INDICATE ON THE PLAN WHAT STANDARD |
| | WAS USED FOR THE SIZING OF THE GREASE INTERCEPTORS. |
| | REFER TO FBC-PLUMBING SECS.1003.2, 1003.3.4. 2ND |
| | REQUEST. |
| | |
| | THE QUESTION WAS NOT ANSWERED; WE ARE LOOKING FOR THE |
| | STANDARD IN SIZING. WAS IT WITH THE ASME A112.14.3, |
| | ASME A112.14.4, ASME A112.14.6, CSA B481.3, OR PDI |
| | G101? |
| | |
| | 4) DONE. |
| | |
| | 5) SHT. P-1.5.05 - DONE AND NEW COMMENT; |
| | |
| | NEW COMMENT, WOULD YOU PLEASE LABEL THE RETURN IN THE |
| | LOOP WHERE THE 3/4 STARTS (HWR) TO WHERE IT GOES UP TO |
| | THE SECOND FLOOR PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6) SHT. P-1.5.06 DONE AND NEW COMMENT; |
| | |
| | A. THE VERBIAGE THAT IT SHALL COMPLY WITH ASSE 1024 IS |
| | WHAT WE LOOK FOR BUT NOT ON THE SHEET MOTIONED. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. THE GUESTROOM DESIGNATED SCF REFERS TO THE 2014 |
| | FIFTH EDITION. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 7) DONE. |
| | |
| | 8) DONE. |
| | |
| | 9) SHT P 3.1.01 DONE AND NEW COMMENT; |
| | |
| | THERE ARE CONDENSATE LINES THAT HAVE A P-TRAP AND UNDER |
| | 2017 FBC M307.2.4 AND P1002.1. EACH TRAP SHALL BE |
| | VENTED TO PERMIT THE ADMISSION OR EMISSION OF AIR SO |
| | THAT THE SEAL OF ANY FIXTURE TRAP SHALL NOT BE |
| | SUBJECTED TO A PRESSURE DIFFERENTIAL OF MORE THAN 1 |
| | INCH OF WATER COLUMN PER THE 2017 FBC SECTION 901.2 |
| | TRAP SEAL PROTECTION. THE CONDENSATE LINE DOES NOT SHOW |
| | ANY VENT TERMINATION AND LOCATION. THEY CANNOT |
| | TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR POSITIVE |
| | PRESSURE TO ALLOW IT TO HAVE A DIFFERENTIAL OF ONE-INCH |
| | WATER COLUMN. WOULD YOU PLEASE PROVIDE DETAIL OF HOW |
| | THEY WILL BE VENTED PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |