| Plan Review Notes For Permit 20121101 |
| Permit Number |
20121101 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-10-15 11:53:06 | HOTEL REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2014 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWING (A-4.2.01) SHOULD SHOW ROOF PLYWOOD AS FIRE | | | RETARDANT PER FBC 603.1 (DRAWING A-0.0.02 SHOWS | | | BUILDING CONSTRUCTION TYPE AS IIA) | | | 2) DRAWING (A-1.2.01) SHOWS ROOM 1204 TO BE 1 HR FIRE | | | RATED - THE DOOR SCHEDULE DOES NOT SHOW THE DOOR HOURLY | | | FIRE RATING AND THE SELF CLOSING AND LATCHING | | | REQUIREMENT FBC TABLE 716.5 AND 716.5.9 | | | | | | |
|