| 2021-06-28 09:12:12 | 1) SHT. A-1.3.01 - THE SINK IN ONE OF THE TREATMENT |
| | ROOMS AND ONE OF THE COUPLE'S SUITES AT THE SPA SHALL |
| | COMPLY WITH FBC-ACCESSIBILITY SECS. 212.3, 606.1. THE |
| | RESPONSE NARRATIVE REFERS TO STAFFING BY "ABLE-BODIED" |
| | EMPLOYEES WHICH HAS NOTHING TO DO WITH THE HEIGHT OF |
| | THE SINKS IN THESE ROOMS. SHOW COMPLIANCE ON THE PLANS |
| | WITH THE ACCESSIBILITY REQUIREMENTS FOR THE SINKS. 2ND |
| | REQUEST. |
| | 2) THE FOLLOWING SHEETS DO NOT BEAR THE DIGITAL |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AS |
| | REQUIRED BY F.A.C. 61G15-23.0001, 61G15-23.004 - |
| | P-0.0.00, P-1.1.00, P-1.1.01A, P-1.1.01B, P-1.3.05B, |
| | P-1.5.01, P-3.0.02B, P-3.0.08. 2ND REQUEST. |
| | 3) SHT. P-1.1.00 - INDICATE ON THE PLAN WHAT STANDARD |
| | WAS USED FOR THE SIZING OF THE GREASE INTERCEPTORS. |
| | REFER TO FBC-PLUMBING SECS.1003.2, 1003.3.4. 2ND |
| | REQUEST. |
| | 4) PLACE MATCHLINES ON THE PLUMBING DRAWINGS ALONG WITH |
| | THE CORRELATING PAGE THAT SHOWS THE CONTINUATION OF THE |
| | PIPING.THE WORD "MATCHLINE " WAS PLACED ON THE PLUMBING |
| | SHEETS WITH NO CORRESPONDING REFERENCE SHEET. 2ND |
| | REQUEST. |
| | 5) SHT. P-1.5.05 - A HOT WATER RECIRCULATION LINE IS |
| | REQUIRED IN THE BANQUET KITCHEN. THERE IS NO HOT WATER |
| | RECIRCULATION LINE SHOWN ON THE FLOOR PRESSURE PLAN FOR |
| | THE BANQUET KITCHEN ON SHT.P-1.401A. FBC-PLUMBING |
| | SEC.607.2. 2ND REQUEST. |
| | 6) SHT. P-1.5.06 - THE COFFEE AND TEA BREWERS, WATER |
| | FILTERS AND ICE MAKER SHALL BE EQUIPPED WITH INDIVIDUAL |
| | BACKFLOW PREVENTION DEVICES COMPLYING WITH ASSE 1024 |
| | PER FBC-PLUMBING SEC. 608.3.THE SODA DISPENSER SHALL BE |
| | EQUIPPED WITH A BACKFLOW PREVENTER COMPLYING WITH ASSE |
| | 1022. THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW |
| | PREVENTION DEVICE COMPLYING WITH ASSE 1020. 2ND |
| | REQUEST. |
| | 7)SHT. P-1.5.07 - DETAIL #1 - SHOW THE CONTINUATION |
| | POINT OF THE GAS LINE ON THE ENLARGED KITCHEN PRESSURE |
| | PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) SHT.P-3.0.01 - A RISER TAG ON THE PLAN CALLS OUT |
| | SAN. RISERS 26 - 28 BUT THERE IS NO RISER SHOWN. |
| | CLARIFY. |
| | 9) SHT. P-3.0.09 - THERE ARE SOME DOWNSPOUTS THAT ARE |
| | NOT SIZED, PART OF THE RISER IS CUT OFF ON THE LEFT |
| | SIDE AND RIGHT SIDE OF THE DRAWING. OF THE DRAWING, |
| | |
| | TIM LARGE |