| 2021-06-16 06:45:45 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20121101 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M-1.3.03A AND M-1.3.04A HAVE THE BATH EXHAUST |
| | DUCT TRAVELING THROUGH THE APARTMENT SHAFT, THROUGH THE |
| | NEIGHBORING TENANTS EXHAUST SHAFT THEN THROUGH THE |
| | NEIGHBORING TENANT?S ROOM AND INTO ANOTHER EXHAUST |
| | SHAFT. THESE CHANGES WERE NOT CLOUDED OR MENTIONED IN |
| | THIS LATEST REVISION SCOPE. PLEASE EXPLAIN WHY THIS |
| | CHANGE IS OCCURRING AND HOW YOU WILL PROTECT THE |
| | PENETRATIONS OF THESE SHAFTS. FBC 717.5.3 |
| | |
| | 2) SHEET M-0.0.02: IN THE EXHAUST FAN SCHEDULE CHART |
| | TE-1, TE-2 AND TE-3 WERE NOT MENTIONED IN THE SCOPE OF |
| | THIS REVISION NOR WERE THEY CLOUDED TO INDICATE A |
| | CHANGE. PLEASE SHOW THESE ON THE ROOF PLAN. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |