| 2021-03-23 10:19:01 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20121101 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1.3.01A: THE SUPPLY DUCT FROM AHU-2 IS |
| | MISSING A FD AT THE RATED WALL AT THE DESIGNATION OF |
| | ?COFFEE?. |
| | |
| | 2) SHEET M-1.3.01A: PLEASE EXPLAIN WHAT (B 1220) IS IN |
| | THE BANQUETTE KITCHEN. |
| | |
| | 3) SHEET M-1.3.01B: PLEASE SHOW THE FD IN THE DUCT |
| | PENETRATING THE RATED WALL AT SECURITY/RECEIVING. |
| | |
| | 4) SHEET M-1.3.01B: PLEASE SHOW THE FD FOR DUCT |
| | PENETRATING RATED WALL IN THE DRY STORAGE ROOM. |
| | |
| | 5) SHEET M-1.3.01B: PLEASE SHOW THE FD IN THE MEN?S |
| | LOCKER ROOM EXHAUST DUCT PENETRATING CORRIDOR WALL. |
| | |
| | 6) SHEET M-1.3.01B: PLEASE EXPLAIN THE 10X10 EXHAUST |
| | DUCT IN WHAT APPEARS TO BE A KITCHEN TO THE LEFT OF THE |
| | MANICURE/PEDICURE ROOM. THIS EXHAUST DUCT IS |
| | PENETRATING A RATED WALL AT THIS ROOM, PLEASE SHOW HOW |
| | THE PENETRATION WILL BE PROTECTED. |
| | |
| | 7) SHEET M-1.4.01: PLEASE SHOW HOW BOTH THE MANICURE |
| | AND THE PEDICURE PROCEDURE MEETS THE REQUIREMENT OF |
| | CONTAINMENT SOURCE WITHIN 12 INCHES OF CHEMICAL |
| | APPLICATION. FBC M 502.20 |
| | |
| | 8) SHEET M-1.4.01: KITCHEN HOOD SYSTEMS MUST HAVE A |
| | SEPARATE PERMIT AND REVIEW. |
| | |
| | 9) SHEET M-1.4.02: KITCHEN AIR BALANCE SCHEDULE MUST |
| | SHOULD BE INCLUDED WITH THE HOOD SYSTEM PERMIT AND |
| | REVIEW. PLEASE DO NOT FORGET THAT ALL EXHAUST, |
| | INCLUDING THE BATHROOMS MUST BE APPLIED. FBC M |
| | |
| | 10) SHEET M-1.5.01: KEY NOTE 1 REFERS TO SHEET M-5.0.03 |
| | DETAIL #5 FOR THE TOILET EXHAUST SUBDUCT REQUIREMENT |
| | THIS SHEET ALONG WITH SEVERAL MORE ARE NOT INCLUDED |
| | WITH THIS SUBMITTAL. PLEASE PROVIDE A COMPLETE |
| | MECHANICAL DESIGN INCLUDING ALL M SHEETS. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |