| Plan Review Notes For Permit 20121099 |
| Permit Number |
20121099 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-25 11:53:51 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE | | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | | BE USED. | | | AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE | | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | | | | | | | | THE VALUATION HAS BEEN ADJUSTED AS THE APPLIED FOR | | | VALUE APPEARS TO BE VERY LOW FOR A 70 SQUARE FOOT | | | ILLUMINATED SIGN (2-SIDES) PER THE MARSHALL VALUATION | | | SERVICE RANGE. THE VALUATION SHOULD BE CLOSER TO THE | | | $10,000.00 AREA (MINIMUM). |
|