| Plan Review Notes For Permit 20121038 |
| Permit Number |
20121038 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-08 14:55:02 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE GENERATOR EXHAUST DISTANCE FROM | | | BUILDING OPENINGS PER FBC R303.5.1 (10 FT) | | | |
|