| 2021-01-21 06:58:42 | 1) PROVIDE AN ENLARGED FLOOR PLAN FOR THE NEW HANDIAP |
| | ACCESSIBLE TOILET ROOM # 526. SHOW THE INSIDE CLEAR |
| | DIMENSIONS (L X W) OF THE TOILET ROOM AND THE LENGTH |
| | AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACES FOR THE |
| | LAVATORY AND THE WATER CLOSET. WPB AND. TO FBC SEC. |
| | 107.2.1. |
| | 2) SHT. AE 101 - SHOW THE REQUIRED CLEAR FLOOR SPACE |
| | AND KNEE AND TOE CLEARANCES FOR THE BREAK ROOM SINK. |
| | SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACE. COMPLY |
| | WITH FBC-ACCESS. SEC. 305, 306, 606.2. |
| | 3) SHT. AE 101 SHOWS TWO SETS OF EXAM ROOMS LABELED #5, |
| | 6,& 7. CLARIFY. |
| | 4) SHT. AE 502 SHOWS GRAB BARS IN A VERTICAL POSITION. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION |
| | PER HE FBC-ACCESS. SEC. 609.4. TTHERE IS NO EXCEPTION |
| | ALLOWING FOR GRAB BARS TO BE INSTALLED IN A VERTICAL |
| | POSITION. |
| | 5) SHT. AE 502 - REAR WALL DETAIL. THE MAXIMUM HEIGHT |
| | OF THE SANITARY NAPKIN DISPOSAL OPERABLE PART SHALL BE |
| | LOCATED A MAXIMUM OF 48 INCHES ABOVE THE FINISH FLOOR |
| | PER FBC-ACCESS. SECS.308 & 309.SSHOW THIS ON THE |
| | DETAIL. |
| | 6) SHT. AE 502 - TOILET FIXTURES AND ACCESSORIES DETAIL |
| | - THE PAPER TOWEL DISPENSER OUTLET FOR THE PAPER TOWELS |
| | SHALL BE LOCATED A MAXIMUM OF 48 INCHES ABOVE THE |
| | FINISH FLOOR. THE DETAIL SHOWS THE PAPER TOWEL OUTLET |
| | ABOVE THIS MAXIMUM HEIGHT. FBC -ACCESS. SECS.308 & 309. |
| | 7) SHT. AE 502 - GENERAL SHEET NOTES #4,5, & 6 REFER TO |
| | THE ANSI A117.1 & THE ADA. THE GOVERNING STANDARD FOR |
| | HANDICAP ACCESSIBILITY IN THE STATE OF FLORIDA IS THE |
| | FLORIDA BUILDING CODE - ACCESSIBILITY VOLUME. EITHER |
| | REVISE THE NOTES TO REFLECT THE FBC OR DELETE THE |
| | NOTES. |
| | 8) SHT. AE 701 - INTERIORS- ROOM FINISH SCHEDULE SHOWS |
| | THE WALLS IN THE TOILET ROOM # 526 AS PAINT. WALLS AND |
| | PARTITIONS WITHIN TWO FEET OF WATER CLOSETS SHALL HAVE |
| | A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OFF |
| | NOT LESS THAN 4 FEET ABOVE THE FLOOR,AND THE MATERIALS |
| | USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT |
| | ADVERSELY AFFECTED BY MOISTURE PER FBC-BUILDING SEC. |
| | 1210.2.2. EPOXY PAINT DOES NOT MEET THE INTENT OF THIS |
| | CODE SECTION. |
| | 9) SUBMIT FIRESTOPPING DETAILS FOR ANY PIPE |
| | PENETRATIONS THROUGH RATED FLOOR AND WALL ASSEMBLIES |
| | PER FBC -BUILDING SECS. 714.3 & 714.4. |
| | 10) SHT. P002 - PLUMBING SPECIFICATIONS - (C) - PIPE & |
| | FITTINGS (2) - DOMESTIC WATER NOTE # ( B) - PVC IS NOT |
| | PERMITTED INSIDE THE BUILDING OR WATER DISTRIBUTION PER |
| | FBC-PLUMBING SEC.605.4 AND TABLE 605.4. |
| | 11) TEMPERED WATER IS REQUIREED AT THE LAVATORY IN THE |
| | ACCESSIBLE TOILET ROOM PER FBC-PLUMBING SEC.416.5. THE |
| | WATER- TEMPERATURE LIMITING DEVICE SHALL COMPLY WITH |
| | ASSE 1070OR CSA B125.33. |
| | 12) SHUTOFF VALVES ARE REQUIRED ON THE WATER SSUPPLY |
| | DROPS TO THE TOILET RROOM, BREAK ROOM SINK AND THE SINK |
| | IN THE WORK AREA.FBC-PLUMBING SEC.606.1, 06.2.. |
| | 13) THE BRANCH VENT FOR THE PLUMBING FIXTURES APPEARS |
| | TO XCEED 40 FET IN DEVELOPED LENGTH. VENNTS EXCEEDING |
| | 40 FEET IN DEVELOPED LENGTH SHALL B INCREASED BY ONE |
| | NOMINAL PIPE SIZE OR THE ENNTIRE DEVELOPED LENGTH OF |
| | THHE VVENT PIPE PER FBC-PLUMBING SEC.906.2. |
| | 14) SHT. P101 - KEYNOTE #1 - CALLS OUT AN 1 1/2 INCH |
| | COLD WATER LINE BUT THERE IS NO SUCH SIZED WATER LLINE |
| | SHOWN ON SHT. P901. |
| | 15) PLANS SHALL DIGITALLY SIGNED AND SEALED PER FL. |
| | ADMIN. CODE RULE 61G1-16.005, 61G15-23.004, |
| | 61G15-23.005. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |